FlexTop 2203
Baumer Temperature measurement

FlexTop 2203

Temperature transmitter

Technical Specifications

Features
  • Specifically for T/C
  • Input: T/C, mV
  • Measuring range -100 to +1820 °C
  • Accuracy better than 5 °C
  • ATEX explosion protection
  • DIN form B housing installation

Detailed Technical Data

Output signal

Damping 0.0 … 30 s , programmable
Accuracy < 0.1 % FSR
TAG No. 15 characters
Load resistance R = (U - 8 V)/23 mA
Power Supply 8 … 35 V DC
Ripple immunity 3 Vrms
Resolution 12 bit
Output Signal 4 … 20 mA , 2 wire
Temperature drift < 0.003 %/K , typical< 0.01 %/K , max..
Up/Down scaling limits 23 mA / 3.5 mA
Reverse polarity protection Yes
Power-on time ≤ 10 s
Supply voltage dalgalanmasının etkisi < 0.01 %/V

Environmental Conditions

Humidity < 98 % RH , condensing
Protection degree (EN 60529) IP 40
Long-term test (transmitter) IEC 770 6.3.2
Vibration (sinüzoidal) (EN 60068-2-6) 1.6 mm p-p (2 … 25 Hz), 4 g (25 … 100 Hz), 1 octave / dk.

COMPLIANCE AND APPROVALS

EMC EN 61000-6-2EN 61000-6-3EN 61326-1
Namur NE21
Explosion protection ATEX II 1 G Ex ia IIC T5/T6ATEX II 3 G Ex ec IIC T5