Housing
Continuous level measurement
Sensing Range
hygienic design / ATEX
Baumer
Level sensors
PBMH - Configurator
Pressure sensor
Technical Specifications
Housing
Continuous level measurement
Sensing Range
hygienic design / ATEX
Detailed Technical Data
Process Connection
Connection variants
"Ölçü çizimleri" see section
Wet part material, membrane
AISI 316L (1.4435)
COMPLIANCE AND APPROVALS
Explosion protection
ATEX II 1/2G Ex ia IIC T4/T6 Ga/GbATEX II 1/2G Ex ia IIC T3/T4/T6 Ga/GbATEX II 1D Ex ia IIIC T (200) 107 °C IP6X DaATEX II 1G Ex ia IIC T4/T6 GaATEX II 1G Ex ia IIC T3/T4/T6 Ga
Performance Features
Pressure type
AbsoluteRelative (gauged)
Long term stability
≤ 0.1 % FSR/a , measuring range > 1 bar≤ 1 mbar , measuring range ≤ 1 bar
Min.. measuring span
0.1 bar
Measuring range
-1 … 40 bar
Basamak response time
≤ 5 ms
Max.. measurement error
± 0.1 % FSR± 0.25 % FSR zero point and range error, non-linearity (terminal base to the line according to), hysteresis and non-repeatability includes (EN 61298-2)Turndown for, this value applied turndown at a ratio of multiply
Temperature coefficient
≤ 0.03 % FSR/10 K , measuring span≤ 0.03 % FSR/10 K , zero point
Max.. measuring rate (turndown)
5 : 1
Standard error of measurement (BFSL)
± 0.04 % FSR± 0.1 % FSR linear olmama, hysteresis and non-repeatability includes (BFSL per spec)Turndown for, this value applied turndown at a ratio of multiply
Max.. measuring range width
40 bar
Compensated temperature range
-40 … 85 °C