Orbitmerret
Sinyal dönüştürücüler
Dijital dönüştürücüler
OMX 333UQC
Technical Specifications
Input Signal
Frekans / Sayıcı
Mounting
DIN ray
Output / Communication
Analog çıkış (mA/V)
Detailed Technical Data
tune
Input
UQC – Input
selectable from menu
0...30/300 V, comparison levels are adjustable from menu or automatic
UQC – Input frequency
0,1 Hz…50 kHz (mode SINGLE)
0,1 Hz…20 kHz (mode UP/DW)
0,1 Hz…20 kHz (UP-DW)
0,1 Hz…20 kHz (mode QUADR. - frequency)
0,1 Hz…10 kHz (mode QUADR. - counter)
(for 50% duty cycle)
UQC – Measurement mode
SINGLE | Counter/frequency
QUADR | Counter/frekans for IRC sensor
UP/DW | Counter/frequency
UP - DW | Counter/frequency
TIME | Stopwatch
RTC | Clock
UQC – Time base
0,5/1/2/5/10 s
UQC – Calibration coefficient
0,00001…999999
UQC – Front setting
0…999999
UQC – Input filtresi
out
5/40/100/1 000 Hz
UQC – Functions
Preset | initial non-zero value, which is always read after resetting the instrument
current value | single setting of the initial value
Summation | registration of numbers during shift operation
External inputs – Number
1 input, contact input
External inputs – Functions
OFF | No function
HOLD | stops the measurement (option
Display - Analog output - Limits)
LOCK | Front panel tuşlarını kilitle
TARA | tare activation
CL.SUM. | Resetting sum
CLR. ST. | input clears (presets) stop-watch/counter, Stop-watch also stops
tune
Display
Signal LED'i
L1, L2 | Limits L1, L2 (red)
Lo, Hi | Signalization, settings and errors (red/green)
tune
Settings
Control
The instrument is controlled and set by two buttons and a DIP açılış the front panel
OM Link
the company's communication interface for running, configuring and updating the device firmware
The OM Link program is also designed for visualising and logging measured values from multiple devices
tune
Device Accuracy and Functions
Temperature coefficient
50 ppm/°C
Accuracy
±0,1 % of range
Speed
0,5…80 measurement/s
Overload capacity
2x
10x (t < 30 ms)
Linearisation
25 noktalı lineer interpolasyon (only OM Link via)
Digital filters
exponential average | 2…100 measurements
rounding | sets the display step
input filter | transmits input signal range 5…1 000 Hz
1/Fr. | filter for frequency conversion to time
Functions
Tare | resets the display on a non-zero input signal
Preset | initial non-zero value, which is read after each counter reset
Summation | number registration upon shift operation
Monitoring function
500 ms
Calibration
at 25°C and 40% relative humidity
tune
Comparators
Type
Digital, adjustable from menu, contact bağlantısı < 50 ms
Mode
Hysteresis | sets the switching point, hysteresis band "Mez ± 1/2 Hys." and time (0 ... 99.9 s) switching delay
C-Pulse | auto counter reset on the preset value
Once | switching ON limit, however it opens only after a counter reset
On Run | output is active while stopwatch is running
Output
1x relay, change contact (250 VAC/30 VDC, 3 A)
2x relay, change contact (250 VAC/30 VDC, 3 A)
1x open collector (30 VDC/100 mA)
2x open collector (30 VDC/100 mA)
tune
Data Outputs
Protocol
ASCII
Data formatı
8 bit + parite none + 1 stop bit (ASCII)
Speed
600…230 400 Baud
RS 485
isolated, max. adresleme: 31 device
tune
Analog Outputs
Type
İzoleli, programlanabilir, 16-bit D / A converter, type and range selectable from menu
Temperature coefficient
15 ppm/°C
Non-linearity
±0,1 % of range
Speed
value değişimine yanıt < 1 ms
Ranges
0...2 V, 0...5 V, 0...10 V, 0...5 mA, 0...20 mA, 4...20 mA
Compensation
600 Ohm/12 V
Error status
of rangeda 4...20mA
error message indicator (<3.0 mA)
current döngüsü kesintisi tespiti
tune
Power supply
Power supply
10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 45 A/1 ms
10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 40 A/1 ms, isolated
Current consumption
< 2 W/2 VA
tune
Operating Conditions
Connection
terminal connection card, cable cross-section < 1,5 mm²
Stabilisation time
within 15 minutes after power-on
Operating temperature
-20°…60°C
Storage temperature
-20°…80°C
Protection class
IP20
Electrical safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC for 1 min. between power supply, input and output
2,5 kVAC 1 min. for input with data/analog output between
Insulation resistance
power supply | 550 V (ZI), 255 V (Di)*
EMC
EN 61326-1
tune
Mechanical Characteristics
Material
PA 66, flame-retardant UL 94 V-I (blue)
Dimensions
25 x 79 x 110 mm (w x h x d)
Installation
DIN rail, width 35 mm