BNS 16 ST1-AS V
Order No 101177221
Article Code 101177221
Certificates cULus ASi-SaW
Schmersal Emniyetli Anahtarlama ve Denetleme Emniyet Sensörleri

BNS 16 ST1-AS V

Product Description

  • IP Rating: IP67 | Voltage: 18 ... 31.6 VDC | Weight: 138 g | Certification: cULus ASi-SaW | PL e

Standards

  • EN IEC 61508

Product Features

  • connector plug M12, bottom, 4-pole_x000D_
  • Safety sensor_x000D_
  • Termoplastik gövde_x000D_
  • Mekanik aşınma yok_x000D_
  • 40 mm x 90 mm x 39 mm_x000D_
  • Entegre AS-Interface_x000D_
  • Gizli montaj mümkün_x000D_
  • Uzun ömürlü_x000D_
  • Yanal hizasızlığa karşı duyarsız_x000D_
  • Kirlenmeye karşı duyarsız_x000D_
  • AS-Interface LED and status display

Technical Specifications

PIN 1 AS-i +
PIN 2 n.c.
PIN 3 AS-Interface -
PIN 4 n.c.
Coding Yes
Category 4
Active Area front taraf
PFH Value 7.42 x 10⁻⁹ /h
AS-i ID Code 0xB
AS-i IO Code 0x0
AS-i Profile S-0.B.F.E
Impact Resistance 30 g / 11 ms
AS-i ID Code 1 0xF
AS-i ID Code 2 0xE
AS-i Version V 2.1
Mission Time 20 Year(s)
Direction of Movement Active to the surface vertical
Gross Weight 138 g
Housing Material Cam elyaf takviyeli termoplastik
Protection Class II
Pollution Degree 3
Connector Position Bottom
Note (PFH Value) up to max. 500,000 switching cycles/year
Sensor Length 38.5 mm
Scope of Delivery Actuator additionally order must be.
Vibration Resistance 10 … 55 Hz, amplitude 1 mm
AS-i Specification Safety Slave
Actuation Element Magnet
IP Protection Class IP67
Max. Response Time 100 ms
Ambient Temperature -25 ... +60 °C
Performance Level e
Sensor Width 40 mm
Operating Principle Magnetic drive
Sensor Height 90 mm
Recommendation (Actuator) BPS 16
AS-i Input Channel 1 Veri bitleri DI 0 / DI 1 = dinamik kod iletimi
AS-i Input Channel 2 Veri bitleri DI 2 / DI 3 = dinamik kod iletimi
Terminal Connection M12 connector plug, 4 pole (A coded)
Suitable SIL Applications 3
AS-i Max. Current Consumption 50 mA
AS-i Output DO 0...DO 3 No function
Mechanical Mounting Conditions Semi-recessed
Note (Switching Distance) All switching distances EN IEC 60947-5-3'e is according to
Note (Repeat Accuracy R) Repeat accuracy R ≤ 0,1 x S ao
AS-i Input Module Address 0
Overvoltage Category III
Rated Operating Voltage 18 ... 31.6 VDC (Reverse polarity protection)
Note (AS-i Parameter Bits) Set the parameter outputs to "1111" (0xF). FID: peripheral error
Guaranteed Opening Distance (ON) Sao 8 mm
AS-i Parameter Bits P0...P3 No function
Impulse Withstand Voltage (Uimp) 0.8 kV
Guaranteed Opening Distance (OFF) Sar 18 mm
Storage/Transport Temperature -25 ... +70 °C
Integrated System Diagnostics Status Yes
Rated Insulation Voltage (Uᵢ) 32 VDC
Note (AS-i Input Module Address) Adres 0'a front set; AS-interface bus master or el type programlama device with changeable
Note (LED Switching Condition Indication) (1) LED yellow: Channel 1 / AS-i SaW Bit 0.1 (2) LED green/red (AS-i duo LED): Supply voltage / communication error / slave address = 0 / periphery error detected (3) LED yellow: Channel 2 / AS-i SaW Bit 2.3