AES 7112.3 24 VAC
Order No 101120016
Article Code 101120016
Certificates cULus
Schmersal Emniyetli Sinyal İşleme Güvenlik İzleme Modülleri

AES 7112.3 24 VAC

Product Description

  • Voltage: 24 VAC | Dimensions: 105mm×96mm×58mm | Weight: 140 g | Certification: cULus | Contacts: 2 NC, 4 NO | PL d

Standards

  • EN ISO 13849-1 EN IEC 61508

Product Features

  • BNS serisi manyetik güvenlik sensörü izleme_x000D_
  • 1 güvenlik kontağı, STOP 0

Technical Specifications

Mounting Fits onto a standard DIN rail per EN 60715
Warning maks. 50.000 switching cycle/year and maks. %80 contact load for
Depth 58 mm
Category 3
General Note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 105 mm
Height 96 mm
PFH Value 1.00 x 10⁻⁷ /h
Number of LEDs 1
Impact Resistance 30 g / 11 ms
EMC Class EMC Directive
Application Note Safety sensor Guard system
Mission Time 20 Year(s)
Gross Weight 140 g
Housing Material Glass-fibre reinforced thermoplastic, ventilated
Contact Material AgSn0
Pollution Degree 2
Vibration Resistance 10...55 Hz, Amplitude 0.35 mm, ± 15 %
Frequency Range 50 Hz 60 Hz
Max. Cable Cross-Section 1.5 mm²
Terminal (Mechanical) Threaded terminal block
Stop Category 0
Ambient Temperature +0 ... +55 °C
Performance Level d
Thermal Test Current 0.20833333333212067
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Mechanical Life (min.) 3,000,000 Cycles
Note (Contact Resistance) In new condition
Reset When Power is Removed Yes
Max. Transmission Resistance 40 Ω
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Suitable SIL Applications 2
Connection Diagram Note BNS series magnetic safety sensor with 1 guard door monitoring. S2'ye ek sensor can be connected. PL c and Category 1'e up to a guard the door assurance below securing for.
Permissible Cable Type Single core solid / esnek
Number of Safety Contacts 1
IP Protection (Mounting Area) IP54
Automatic Reset Function Yes
Current Utilization Cat. AC-15 0.08333333333212067
Current Utilization Cat. DC-12 0.1 A
Current Utilization Cat. DC-13 0.08333333333212067
Overvoltage Category III
Electrical Power Consumption 1.5 W
Min. Switching Capacity 10 mA
Rated Operating Voltage 24 VAC
AC Control Voltage 50Hz min. 20.4 VAC
AC Control Voltage 60Hz min. 20.4 VAC
Voltage Utilization Cat. AC-15 250 VAC
Voltage Utilization Cat. DC-12 24 VDC
Voltage Utilization Cat. DC-13 24 VDC
IP Protection (Terminal Block) IP20
Max. Switching Capacity 0.08333333333212067
AC Control Voltage 50Hz max. 26.4 VAC
AC Control Voltage 60Hz max. 26.4 VAC
Impulse Withstand Voltage (Uimp) 4 kV
Emergency Release Delay 20 ms
Storage/Transport Temperature -25 ... +70 °C
Integrated System Diagnostics Status Yes
Pull-In Delay After RESET 20 ms
Displayed Operating States Yetkili operation
Number of NO (Normally Open) Contacts 4
Release Delay on Power Failure 80 ms
Number of NC (Normally Closed) Contacts 2
Pull-In Delay on Automatic Start 100 ms
shopping_cart

Quote Cart

shopping_cart

Your cart is empty.

You can add products from product pages.

compare_arrows Compare 0 / 3
Canlı sohbet çok yakında aktif edilecektir.