Order No
103032190
Article Code
103032190
Certificates
TÜV cULus FCC IC ANATEL UKCA
Schmersal
Emniyetli Anahtarlama ve Denetleme
Solenoid Kilitler
AZM201Z-CC-T-1P2PW-2719-1
Product Description
- • IP Rating: IP66/IP67 | Voltage: 24 VDC | Weight: 534 g | PL d
Standards
- • EN ISO 13849-1 EN IEC 61508
Product Features
- • Açmak için güç gerekli_x000D_
- • Kapı kilitleme izleniyor_x000D_
- • Termoplastik gövde_x000D_
- • Sensör zincirinin maks. uzunluğu 200 m_x000D_
- • Kendinden izlemeli seri kablolama_x000D_
- • Coding in accordance to ISO 14119 by using RFID-Technology_x000D_
- • Çalışma koşullarını gösteren 3 LED_x000D_
- • Sensör teknolojisi aktüatör ve kilit arasında ±5 mm dikey ve ±1,5 mm yatay ofset sağlar_x000D_
- • Menteşeli ve kızaklı koruyucular için uygun_x000D_
- • Akıllı diagnostik_x000D_
- • Manuel açma_x000D_
- • Koruma sınıfı IP66, IP67_x000D_
- • High holding force 2000 N_x000D_
- • symmetrical construction form, assembly on 40mm profiles_x000D_
- • OSSD safety outputs_x000D_
- • Emergency exit / Emergency release suitable for retrofitting
Technical Specifications
Note
All belirtimler iletken end included.
Coding
Universal coding
Category
2
General Note
Actuator unit solenoid in the lock fitted remains as long as, lock opened guard device again can be locked.
PFD Value
8.90 x 10⁻⁴
PFH Value
1.00 x 10⁻⁸ /h
Impact Resistance
30 g / 11 ms
Cable Entry
1 x M20
Mission Time
20 Year(s)
Min. Wire Cross-Section
23 AWG
Series Connection
Yes
Gross Weight
534 g
Housing Material
Cam elyaf takviyeli termoplastik
Protection Class
III
Max. Wire Cross-Section
15 AWG
Locking Force
30 N
Pollution Degree
3
Max. Relative Humidity
0.93
Min. Cable Cross-Section
0.25 mm²
Note (Relative Humidity)
Non-condensing, non-icing
Sensor Length
50 mm
Scope of Delivery
Actuator additionally order must be. Triangular key for AZM 201
Vibration Resistance
10 … 150 Hz, amplitude 0.35 mm
Force to Open
Yes
Max. Cable Cross-Section
1.5 mm²
Max. Risk Time
200 ms
Manual Lock Release
Yes
Operating Current
50 mA
24V Current Consumption
5 mA
IP Protection Class
IP66 IP67
Short-Circuit Detection
Yes
Ambient Temperature
-25 ... +60 °C
Performance Level
d
RFID Frequency Band
125 kHz
Sensor Width
40 mm
Operating Voltage
24 VDC -15% / +10% (stabilized PELV power source)
Operating Principle
RFID
Mechanical Life (min.)
1,000,000 Cycles
Sensor Height
220 mm
Recommendation (Actuator)
AZ/AZM201-B1 AZ/AZM201-B30
Switching Thresholds
−3 V … 5 V (Low) 15 V … 30 V (High)
Note (Series Connection)
Unlimited number of devices; observe the external line fuse; max. 31 devices when using serial diagnostics (SD)
Cross-Circuit Detection
Yes
Fixing Screw Type
2x M6
Terminal Connection
Spring pulley connection
Max. Actuation Speed
0.2 m/s
Max. Leakage Current (Ir)
0.5 mA
Suitable SIL Applications
2
Safety Functions
Yes
Max. Installation Altitude
2,000 m
Max. Test Pulse Duration
0.5 ms
Max. Holding Force Fmax
2,600 N
Solenoid Lock Monitored
Yes
Permissible Cable Type
Single core solid / very core solid / esnek
Number of Safety Contacts
2
Max. Ready Time
4,000 ms
Current Utilization Cat. DC-13
0.05 A
Min. Test Pulse Interval
100 ms
Overvoltage Category
III
Magnet Release Time
1
Rated Operating Voltage
24 VDC
Typical Test Pulse Interval
1000 ms
Voltage Utilization Cat. DC-13
24 VDC
Safety Inputs Definition
X1 and X2
Max. Voltage Drop (Ud)
4 V
Max. Fixing Screw Torque
8 Nm
Max. Transmitter RFID Output
-6 dBm
Magnet Control Definition
IN
Impulse Withstand Voltage (Uimp)
0.8 kV
Control Elements Design
Short devre resistant, p-type
Storage/Transport Temperature
-25 ... +85 °C
Integrated System Diagnostics Status
Yes
Coding Level (EN ISO 14119)
Low
Max. Sensor Chain Length
200 m
Note (Sensor Chain Length)
Cable length and cross-section change the voltage drop depending on the output current
Note (Clamping Force FZh)
AZ/AZM201-B30 actuator with when used 1.000 N, indoor space use for.
Holding Force FZh (EN ISO 14119)
2,000 N
Safety Outputs Definition
Y1 and Y2
Rated Insulation Voltage (Uᵢ)
32 VDC
Note (Clamping Force Fmax)
1,300 N in combination with an AZ/AZM201-B30 actuator, for indoor mounting.
Diagnostic Outputs Definition
OUT
Max. Switching Frequency (Approx.)
1 Hz
Housing Cover Screw Torque (Min.)
0.7 Nm
Required Rated Short-Circuit Current
100 A
External Wire and Device Fuse Rating
4A gG
Housing Cover Screw Torque (Max.)
1 Nm
Magnet ON Peak Current Consumption
700 mA / 100 ms
ZVEI CB24I Sink Classification
C1 C2
ZVEI CB24I Source Classification
C2
Magnet ON Average Current Consumption
200 mA
Typical Idle Operating Current (I₀)
50 mA
Note (LED Switching Condition Indication)
Operating status: LED green / Fault / functional failure: LED red / Supply voltage UB: LED green
Rated Operating Current (Safety Outputs)
250 mA
Max. Response Time (Actuator to Safety Output Off)
100 ms
Max. Response Time (Safety Input to Safety Output Off)
1.5 ms