AZS 2305.1 110 VAC
Order No 101126704
Article Code 101126704
Certificates cULus
Schmersal Emniyetli Sinyal İşleme Güvenlik Rölesi ve Kontrol Modülleri

AZS 2305.1 110 VAC

Product Description

  • • Voltage: 110 VAC | Dimensions: 55mm×75mm×110mm | Weight: 445 g | Certification: cULus | Contacts: 1 NC, 1 NO | PL d

Standards

  • • EN IEC 61508

Product Features

  • • Fail-safe delay timer_x000D_
  • • Time adjustable from 0,1 s to 99 min_x000D_
  • • 3 safety contacts_x000D_
  • • 2 sinyal çıkışı

Technical Specifications

Note All belirtimler iletken end included.
Mounting Fits onto a standard DIN rail per EN 60715
Depth 110 mm
Category 3
Faults Safety relay failing to pull in or drop out. Fault in the safety monitoring module input/relay control circuits. Timing difference between channel I and II. Cross-connection to the input lines. Disconnection of the input connections.
General Note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 55 mm
Height 75 mm
PFH Value 1.00 x 10⁻⁷ /h
Number of LEDs 1
Impact Resistance 30 g / 11 ms
EMC Class EMC Directive
Application Note Fail-safe delay timer
Mission Time 20 Year(s)
Gross Weight 445 g
Housing Material Cam elyaf takviyeli termoplastik
Pollution Degree 2
Vibration Resistance 10 ... 55 Hz, Amplitude 0.35 mm
Frequency Range 50 Hz 60 Hz
Clip Tightening Torque 0.4 Nm
Max. Cable Cross-Section 4 mm²
Ambient Temperature +0 ... +55 °C
Performance Level d
Operating Voltage 110 VAC -15 % / +15 %
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Note (Contact Resistance) In new condition
Reset When Power is Removed Yes
Max. Transmission Resistance 40 Ω
Note (ISD - Faults) The following fault safety monitoring modules by kaydedilir and ISD by is shown.
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Terminal Connection Solid or esnek, threaded terminal block M20 x 1,5
Suitable SIL Applications 2
Connection Diagram Note Connection diagram, guard door closed and enerji cut off in the state is shown. ISD tables in the appendix. Hazardous operation stopping movements for PL d and Category 3'e up to. Solenoid lock specified duration when exceeded opens.
Number of Safety Contacts 3
IP Protection (Mounting Area) IP54
Automatic Reset Function Yes
Current Utilization Cat. AC-15 0.08333333333212067
Current Utilization Cat. DC-12 0.1 A
Current Utilization Cat. DC-13 0.08333333333212067
Overvoltage Category III
Electrical Power Consumption 5 W
Min. Switching Capacity 10 mA
Rated Operating Voltage 110 VAC
Number of Signal Outputs 2
AC Control Voltage 50Hz min. 20.4 VAC
AC Control Voltage 60Hz min. 20.4 VAC
Voltage Utilization Cat. AC-15 250 VAC
Voltage Utilization Cat. DC-12 24 VDC
Voltage Utilization Cat. DC-13 24 VDC
IP Protection (Terminal Block) IP20
Max. Switching Capacity 0.08333333333212067
Earth Connection Detection Yes
AC Control Voltage 50Hz max. 26.4 VAC
AC Control Voltage 60Hz max. 26.4 VAC
Input Signal LOW (Signal 0) 0 … 2 VDC
Impulse Withstand Voltage (Uimp) 4 kV
Input Signal HIGH (Signal 1) 10 … 30 VDC
Emergency Release Delay 20 ms
Storage/Transport Temperature -25 ... +70 °C
Integrated System Diagnostics Status Yes
Pull-In Delay After RESET 20 ms
Number of NO (Normally Open) Contacts 1
Release Delay on Power Failure 80 ms
Number of NC (Normally Closed) Contacts 1
Pull-In Delay on Automatic Start 100 ms
Number of Undelayed Semiconductor Outputs (with Signal Function) 2