Depth
121 mm
Faults
Fault on the input circuits or the relay control circuits of the safety monitoring module | Interruption of the switch connections | Failure of door contacts to open or close | Failure of the safety relay to pull-in or drop-out | Cross-wire or short-circuit monitoring of the switch connections
Montaj
Snaps onto standard DIN rail to EN 60715
Notice
for max. 50 000 switching cycles/year and max. 80% contact load | Discontinued product
Kategori
3
Genel Not
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Genişlik
22.5 mm
PFH value
1.00 x 10⁻⁷ /h
EMC rating
EMC-Directive
Yükseklik
100 mm
Kablo Kesiti
0.25 mm² ... 2.5 mm²
Voltage type
AC
Darbe Dayanımı
30 g / 11 ms
Stop-Category
0
Görev Süresi
20 Year(s)
Net Ağırlık
165 g
Number of LEDs
1
Ripple voltage
10 %
Climatic stress
BG-GS-ET-14 | IEC 60947-5-3
Frequency range
50 Hz | 60 Hz
Brüt Ağırlık
165 g
Gövde Malzemesi
Glass-fibre reinforced thermoplastic, ventilated
Kontak Malzemesi
Ag-Ni 10 and 0.2 µm gold-plated
Kirlenme Derecesi
2
Min. Kablo Kesiti
0.25 mm²
Operating voltage
24 VAC -15 % / +10 %
Titreşim Dayanımı
10...55 Hz, Genlik 0.35 mm, ± %15
Maks. Kablo Kesiti
2.5 mm²
Note (ISD -Faults)
The following faults are registered by the safety monitoring modules and indicated by ISD.
Ortam Sıcaklığı
+0 ... +55 °C
Performans Seviyesi
d
Termal Test Akımı
6 A
Mekanik Ömür (min.)
20 000 000
Allowed type of cable
solid single-wire | flexible
Note (Wiring diagram)
The ISD tables (Intergral System Diagnostics) for analysis of the fault indications and their causes are shown in the appendix. | To secure 2 guard doors up to PL d and Category 3 | Expansion of enable delay time: The enable delay time can be increased from 0.1 s to 1 s by changing the position of a jumper link connection under the cover of the unit. | If one or two external relays or contactors are used to switch the load, the system can then only be classified in Category 3 to EN ISO 13849-1, if exclusion of the fault “Failure of the external contactors” can be substantiated and is documented, e.g. by | The wiring diagram is shown with guard doors closed and in de-energised condition. | Monitoring 2 guard door(s), each with a magnetic safety sensor of the BNS range
Terminal designations
IEC/EN 60947-1
Terminal Bağlantısı
Screw terminals
Cross-circuit detection
Yes
Input resistance at GND
2 000 Ω
Number of inputs for NC
2
Number of inputs for NO
1
Wire breakage detection
Yes
Automatic reset function
Yes
Min. Ortam Sıcaklığı
+0 °C
Note (Delivery capacity)
Not available!
Güvenlik Kontak Sayısı
1
Maks. Ortam Sıcaklığı
+55 °C
Note (Contact resistance)
in new state
Earth connection detection
Yes
Tightening torque of Clips
0.6 Nm
Utilisation category DC-12
24_0.1
Yardımcı Kontak Sayısı
2
Aşırı Gerilim Kategorisi
III
Contact resistance, maximum
0.1 Ω
Nominal Çalışma Voltajı
24 VAC | 24 VAC -15% / +10% | 24 VDC -10%/+20%, residual ripple max. 10%
Switching capacity, maximum
250 VAC | 2 A | 24 VDC | 8 A
Switching capacity, minimum
10 VDC | 10 mA
Electrical power consumption
5 W
Input signal, LOW Signal "0"
0 … 2 VDC
Number of signalling outputs
2
Input signal, HIGH Signal "1"
10 … 30 VDC
Note (application conditions)
Safety sensor | Guard system
Conduction resistance, maximum
40 Ω
Darbe Dayanım Gerilimi (Uimp)
4 kV
Depolama / Taşıma Sıcaklığı
-25 ... +70 °C | -25 ... +75 °C
Pull-in delay at RESET, typically
20 ms
Current, Utilisation category AC-15
6 A
Current, Utilisation category DC-12
0.1 A
Current, Utilisation category DC-13
6 A
Integral system diagnostics, status
Yes
Voltage, Utilisation category AC-15
230 VAC
Voltage, Utilisation category DC-12
24 VDC
Voltage, Utilisation category DC-13
24 VDC
Rated control voltage at DC, maximum
28.8 VDC
IP Degree of protection of the enclosure
IP40
Rated control voltage at AC 50 Hz, maximum
26.4 VAC
Rated control voltage at AC 60 Hz, maximum
26.4 VAC
Storage and transport temperature, maximum
+70 °C
Storage and transport temperature, minimum
-25 °C
Rated AC voltage for controls at DC minimum
20.4 VDC
Reset after disconnection of supply voltage
Yes
IP Degree of protection of clips or terminals
IP20
Rated AC voltage for controls, 50 Hz, minimum
20.4 VAC
Rated AC voltage for controls, 60 Hz, minimum
20.4 VAC
Drop-out delay in case of emergency, typically
20 ms
IP Degree of protection of the installation space
IP54
Drop-out delay in case of power failure, typically
80 ms
Pull-in delay at automatic start, maximum, typically
100 ms
Safety Integrity Level (SIL), suitable for applications in
2
Number of undelayed semi-conductor outputs with signaling function
2