Article No
11086906
Housing
≤ 0.25 - 0.3 % FS
Sensing Range
ISO 2852 (Tri-Clamp), DN 25; 33.7; 38, Ø 50.5 (C04)
Baumer
Pressure sensors
PBMH-24B19AA14481202000
Pressure sensor
Technical Specifications
Article No
11086906
Housing
≤ 0.25 - 0.3 % FS
Sensing Range
- ISO 2852 (Tri-Clamp), DN 25
- 33.7
- 38, Ø 50.5 (C04)
Detailed Technical Data
PROSES BAĞLANTISI
Connection variants
ISO 2852 (Tri-Clamp), DN 33.7; 38, Ø 50.5
Wet part material, membrane
AISI 316L (1.4435)
PERFORMANS ÖZELLIKLERI
Pressure type
Absolute
Long term stability
≤ 0.1 % FSR/a
Measuring range
0 … 4 bar
Max.. measurement error
0.25 % FSR Zero point and range error, non-linearity (terminal base to the line according to), hysteresis and non-repeatability includes (EN 61298-2)
Temperature coefficient
≤ 0.03 % FSR/10 K , measuring span≤ 0.03 % FSR/10 K , zero point
Yükselme time (%10 … %90)
≤ 5 ms
Max.. measuring rate (turndown)
5 : 1
Standard error of measurement (BFSL)
0.1 % FSR linear olmama, hysteresis and non-repeatability includes (BFSL per spec)
Compensated temperature range
-40 … 85 °C