Orbitmerret
Paperless Recorder
Paperless Recorder - Cards
OMR card - IN.13 Paperless Recorder - Cards
Orbit Merret OMR card - IN.13 features frequency / Counter input signal and plug-in card (OMR 700 slot) mounting.
Technical Specifications
Input Signal
Frequency / Counter
Mounting
Plug-in card (OMR 700 slot)
Detailed Technical Data
tune
Input
* – Number of inputs
2 inputs
UQC – Input
- • on contact, TTL, NPN/PNP, Line
- • 5/10/12/24/30 V
UQC – Input frequency
0,1 Hz…1 MHz
UQC – Calibration coefficient
yes
UQC – Front setting
yes
UQC – Input filtresi
- • 100/200/500 µs
- • 1/2/5/10/20/50/100/200/500 ms
- • 1/2/5/10/20/50 s
- • 1/2/5/10 min
tune
Device Accuracy and Functions
Temperature coefficient
50 ppm/°C
Accuracy
- • ±0,05 % of range
- • (frequency)
Overload capacity
- • 2x
- • 10x (t < 30 ms)
Functions
Tare | resets the display on a non-zero input signal
Monitoring function
500 ms
Calibration
at 25°C and 40% relative humidity
tune
Power supply
Power supply
internal bus 3,3 VDC,24 VDC
Current consumption
< 2,5 W
tune
Operating Conditions
Connection
terminal connection card, cable cross-section < 1,5 mm²
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
Electrical safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC for 1 min. between bus and inputs
Insulation resistance
input, bus | 300 V (ZI), 150 V (Di)*
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
tune
Mechanical Characteristics
Dimensions
65 x 98 mm
Installation
plug-in card