Orbitmerret
Signal converters
Digital transducers
OMX 333iUNI Digital transducers
Orbit Merret OMX 333iUNI features universal (multi-input), DIN rail mounting and analog output (mA/V).
Technical Specifications
Input Signal
Universal (multi-input)
Mounting
DIN rail
Output / Communication
Analog output (mA/V)
Detailed Technical Data
tune
Input
* – Number of inputs
1 input
DC – Range
- • selectable from menu
- • ±60 mV
- • > 10 MOhm
- • Input 3
- • ±75 mV
- • > 10 MOhm
- • Input 3
- • ±100 mV
- • > 10 MOhm
- • Input 3
- • ±150 mV
- • > 10 MOhm
- • Input 3
- • ±300 mV
- • > 10 MOhm
- • Input 3
- • ±1000 mV
- • > 10 MOhm
- • Input 3
- • ±20 V
- • > 1 MOhm
- • Input 1
- • ±40 V
- • > 1 MOhm
- • Input 1
- • ±100 mA
- • > 200 mV
- • Input 5
PM – Range
- • selectable from menu
- • ±2 V
- • 1 MOhm
- • input 1
- • ±5 V
- • 1 MOhm
- • input 1
- • ±10 V
- • 1 MOhm
- • Input 1
- • ±5 mA
- • < 200 mV
- • input 5
- • ±20 mA
- • < 200 mV
- • input 5
- • 4…20 mA
- • < 200 mV
- • input 5
OHM – Range
- • selectable from menu
- • 0…100 Ohm
- • 0…300 Ohm
- • 0…1 kOhm
- • 0…3 kOhm
- • 0…10 kOhm
- • 0…30 kOhm
- • 0…100 kOhm
- • 0...300 kOhm (only for 2 or 4-wire connection)
OHM – Connection
2, 3 or 4-wire
RTD – Type
- • selectable from menu
- • Pt 100/500/1000, 3850 ppm/°C
- • -50°...450°C
- • Pt 100 3920 ppm/°C
- • -50°...450°C
- • Pt 50 3910 ppm/°C
- • -200°...1100°C
- • Pt 100 3910 ppm/°C
- • -200°...450°C
RTD – Connection
2, 3 or 4-wire
NTC – Type
- • selectable in the menu
- • NTC1 2k2, B2585=3600 (-40°...125°C)
- • NTC2 2k0, B2585=3528 (-40°...125°C)
- • NTC3 10k, B2585=3435 (-40°...125°C)
- • NTC4 10k, B2585=3977 (-40°...125°C)
- • NTC5 12k, B2585=3740 (-40°...125°C)
- • NTC6 20k, B2585=4263 (-40°...125°C)
NTC – Connection
2, 3 or 4-wire
PTC – Type
KTY 81/210
PTC – Connection
2,3 or 4-wire
Ni – Type
- • selectable from menu
- • Ni 1 000/10 000 with 5 000 ppm/°C
- • -50°…250°C
- • Ni 1 000/10 000 with 6 180 ppm/°C
- • -50°…250°C
Ni – Connection
2, 3 or 4-wire
Cu – Type
- • selectable from menu
- • Cu 50/100 with 4 260 ppm/°C
- • -50°…200°C
- • Cu 50/100 with 4 280 ppm/°C
- • -200°…200°C
DU – Potentiometer power supply
1,65 VDC/3 mA, potentiometer resistance > 500 Ohm
External inputs – Number
2 input, contact input
External inputs – Functions
- • OFF | No function
- • HOLD | stops the measurement (option: Display - Analog output - Limits)
- • LOCK | Front panel tuşlarını kilitle
- • TARA | tare activation
- • NUL. TA. | resets the tare
- • NUL. M.M. | resets the min./max. value
- • ROZ.LIM. | Relay/OC opening (type TRVALE)
- • VZOREK | Start of a single measurement
- • HLD.MIN | HOLD - Minimum value*
- • HLD.MAX | HOLD - Maximum value*
- • HLD.M-M | HOLD - MAX-MIN value*
- • * | Value is calculated from the period since the previous activation of the external input
tune
Settings
Control
The device is controlled and set by two buttons on the front panel
İsteğe bağlı functions
- • TARE | Dara function activation
- • Teach-in | setting the analog input range
OM Link
- • the company's communication interface for running, configuring and updating the device firmware (microUSB)
- • The OM Link program is also designed for visualising and logging measured values from multiple devices
tune
Device Accuracy and Functions
Temperature coefficient
50 ppm/°C
Accuracy
- • 0,05 % of range (DC, PM)
- • 0,07 % of range
- • 0,1 % of range (OHM - 100/300 k)
Soğuk point measurement accuracy
±1,5°C
Speed
- • 1…400 measurements/s
- • the rate of 400 meas./s applies with FFT signal filtering
Overload capacity
- • 2x
- • 10x (t < 30 ms)
- • Tel kompanzasyonu (RTD, OHM): < 30 Ohm
Soğuk point kompanzasyonu
ayarlanabilir -20°…99°C, automatic
Linearisation
linear interpolation in 100 points (only via OM Link)
Digital filters
- • arithmetic average | 2…100 measurements
- • floating average | 2…30 measurement
- • exponential average | 2…100 measurement
- • rounding | setting of a fixed step for value changes
Functions
- • Tare | resets the display on a non-zero input signal
- • Fixed dara | önceden ayarlı fixed dara value
- • Min/max. value | measurement sırasında ulaşılan min./max. value kaydeder
- • Tepe value | display only max. or min. değerleri gösterir
- • Teach-in | semiautomatic regime of input calibration
- • Simulation | simulation of the input signal/device function
- • Delayed start | time during which no measurement is performed after the device is connected to the power supply
Mat. functions
polynomial, inverse polynomial, 1/x, logarithm, exponential, power, root
Monitoring function
500 ms
Calibration
at 25°C and 40% relative humidity
tune
Comparators
Number
2 output
Type
Digital, adjustable from menu, contact bağlantısı < 30 ms
Mode
- • AKT.NAD | Active above the set value
- • AKT.POD | Active below the set value
- • OKENKO | Start, End, Hysteresis, Delay
- • DAVKA | Period, Time
Relay functions
- • SW.ON | contact closed when active
- • SW.OFF | contact open when active
- • PULSE | closes once for a moment
- • LATCH | contact on until disarmed
Output
- • 2x relay, change contact (250 VAC/50 VDC, 3 A)
- • 2x open collector (30 VDC/100 mA)
tune
Data Outputs
Output sayısı
1 output
Type
RS 485, isolated
Protocol
MODBUS - RTU
Data formatı
- • Format | 8bit + parity + stop bit
- • Parity | none / even / odd
- • Stop bit | 1 / 1.5 / 2
Speed
600…230 400 Baud
Address
MODBUS | < 246 instruments
Line termination
by internal resistor 120 Ohm
tune
Analog Outputs
Output sayısı
1 output
Type
İzoleli, programlanabilir, 16-bit D / A converter, type and range selectable from menu
Temperature coefficient
15 ppm/°C
Non-linearity
±0,1 % of range
Accuracy
±0,02 % full scale
Speed
value değişimine yanıt < 1 ms
Ranges
- • 0…2 / 5 / 10 V, ±10 V, resistive load > 1 k?
- • 0…5 / 20 mA / 4…20 mA, comp. < 600 Ohm / V
Error status
- • error message indicator (<3.0 mA)
- • current döngüsü kesintisi tespiti
tune
Sensor supply
Fixed
24 VDC/60 mA, isolated
tune
Power supply
Power supply
10…30 VDC/24 VAC, ±10 %, PF > 0,4, I < 45 A/1 ms, isolated
Current consumption
< 2,4 W/2,6 VA
Power supply protection
protected by a fuse inside the device
tune
Operating Conditions
Connection
terminal connection card, cable cross-section < 1,5/2,5 mm²
Stabilisation time
within 5 minutes after power-on
Operating temperature
-20°…60°C
Storage temperature
-20°…80°C
Operating humidity
< 95 % relative nem, yoğuşmayan
Protection class
IP20
Electrical safety
EN 61010-1, A2
Dielectric strength
- • 2,5 kVAC for 1 min. between power supply and input
- • 2,5 kVAC for 1 min. between input and output
- • 4 kVAC for 1 min. between input and relay output
Insulation resistance
power supply | 300 V (ZI)*
EMC
EN 61326-1
RoHS
IEC 63000 : 2018
Seismic capacity
IEC/IEEE 60980-344 ed. 1.0:2020, par 6,9
Mechanical dayanıklılık
EN 60068-2-6 ed. 2:2008