Schmersal AES 1185.3 24 VAC
Order No 101131929
Certificates cULus
Schmersal Safe Signal Processing Security Relay and Control Modules

AES 1185.3 24 VAC Security Relay and Control Modules

Schmersal AES 1185.3 24 VAC features cam elyaf takviyeli termoplastik housing material, +0 ... +55 °C ambient temperature, 110 mm depth and 22.5 mm width.

Product Description

  • • Voltage: 24 VAC
  • • Dimensions: 22.5mm×75mm×110mm
  • • Weight: 150 g
  • • Certification: cULus
  • • Contacts: 3 NC, 3 NO
  • • PL d

Standards

  • • EN ISO 13849-1
  • • EN IEC 61508

Product Features

  • • BNS series magnetic safety sensor monitoring
  • • 1 safety contact, STOP 0

Technical Specifications

Mounting Fits onto a standard DIN rail per EN 60715
Warning for max. 50.000 switching cycles/year and max. 80% contact load
Depth 110 mm
Category 3
Faults Failure of the safety relay to pull in or drop out; door contacts failing to open or close; cross-wire or short-circuit monitoring of the switch connections; disconnection of the switch connections; fault in the input circuits or relay control circuits of the safety monitoring module; fault or malfunction of the safety relay
General note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 22.5 mm
Height 75 mm
PFH value 1.00 x 10⁻⁷ /h
Number of LEDs 1
Shock resistance 30 g / 11 ms
EMC Class EMC Directive
Application Note Safety sensor, guard system
Mission time 20 Year(s)
Gross weight 150 g
Housing Material Glass-fibre reinforced thermoplastic
Contact material Ag-Ni, Au
Pollution degree 2
Vibration resistance 10...55 Hz, Amplitude 0.35 mm, ± 15 %
Frequency Range 50 Hz 60 Hz
Clip Tightening Torque 0.6 Nm
Max. cable cross-section 2.5 mm²
Number of NO Inputs 3
Number of NC Inputs 3
Terminal (Mechanical) Screw terminals
Climatic Resistance BG-GS-ET-14 IEC 60947-5-3
Ripple Voltage 10 %
Stop Category 0
Ambient Temperature +0 ... +55 °C
Performance level d
Conventional thermal current 4 A
Operating voltage 24 VDC -15% / +10% (stabilised PELV power supply)
Feedback Circuit Yes
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Mechanical life (min.) 50,000,000 Cycles
Note (Contact Resistance) In new condition
Terminal Definitions IEC/EN 60947-1
Reset When Power is Removed Yes
Max. Transmission Resistance 40 Ω
Note (ISD - Faults) The following faults are registered by the safety monitoring modules and indicated by the ISD.
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Suitable SIL Applications 2
Connection Diagram Note The hinge axis must be 5 mm above. Minimum actuating radius on hinged guards 35 mm. Actuator not available separately.
Permitted cable type Single-core rigid / flexible
Number of safety contacts 1
IP Protection (Mounting Area) IP54
Automatic Reset Function Yes
Current Utilization Cat. AC-15 6 A
Current Utilization Cat. DC-12 0.1 A
Current Utilization Cat. DC-13 6 A
Overvoltage category III
Electrical Power Consumption 5 W
Min. Switching Capacity 10 mA
Rated operating voltage 24 VAC
AC Control Voltage 50Hz min. 20.4 VAC
AC Control Voltage 60Hz min. 20.4 VAC
Voltage Utilization Cat. AC-15 230 VAC
Voltage Utilization Cat. DC-12 24 VDC
Voltage Utilization Cat. DC-13 24 VDC
IP Protection (Terminal Block) IP20
Max. Switching Capacity 2 A
Earth Connection Detection Yes
AC Control Voltage 50Hz max. 26.4 VAC
AC Control Voltage 60Hz max. 26.4 VAC
Input Signal LOW (Signal 0) 0 … 2 VDC
Rated impulse withstand voltage (Uimp) 4 kV
Input Signal HIGH (Signal 1) 12 … 30 VDC
Emergency Release Delay 20 ms
Storage/transport temperature -25 ... +70 °C
Integrated System Diagnostics Status Yes
Pull-In Delay After RESET 20 ms
DC Min. Rated Control Voltage 20.4 VDC
DC Max. Rated Control Voltage 28.8 VDC
Number of NO (Normally Open) Contacts 3
Release Delay on Power Failure 80 ms
Number of NC (Normally Closed) Contacts 3
Pull-In Delay on Automatic Start 100 ms