AES 6112
Order No 101112461
Certificates cULus
Schmersal Safe Switching and Monitoring Emniyet Konum Şalterleri (PS Serisi)

AES 6112

AES 6112 — Schmersal product. Key specifications: Housing Material: Glass-fibre, reinforced thermoplastic; Ambient Temperature: +0 ... +55 °C; Terminal connection: Screw terminals; Depth: 58 mm; Mounting: Snaps onto standard DIN rail to EN 60715. Article number: 101112461. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • Ağırlık: 125 g
  • • Sertifika: cULus

Standards

  • • EN IEC 60947-5-3
  • • EN IEC 61508
  • • BG-GS-ET-14
  • • EN IEC 60947-5-5
  • • EN IEC 60947-5-1
  • • EN IEC 60204-1
  • • EN IEC 60947-1
  • • EN ISO 13849-1
  • • BG-GS-ET-20
  • • EN IEC 62061

Product Features

  • • NOTICE: Not available! (Replacement: AES 1112)
  • • Monitoring of BNS range magnetic safety sensors
  • • 1 safety contact, STOP 0

Technical Specifications

Depth 58 mm
Mounting Snaps onto standard DIN rail to EN 60715
Notice for max. 50,000 switching cycles/year and max. 80% contact load
Category 3
General note Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Width 48 mm
PFH value 1.00 x 10⁻⁷ /h
EMC rating EN 61000-4-6 | EN 61000-4-3 | IEC 61000-6-2
Height 96 mm
Cable Cross-Section 1.5 mm²
Voltage type DC
Shock resistance 30 g / 11 ms
Stop-Category 0
Mission time 20 Year(s)
Net Ağırlık 125 g
Number of LEDs 1
Frequency range 50 Hz | 60 Hz
Gross weight 125 g
Housing Material Glass-fibre, reinforced thermoplastic
Contact material AgCdO
Pollution degree 2
Operating voltage 24 VDC -15 % / +15 %
Vibration resistance 10...55 Hz, Amplitude 0.35 mm, ± 15 %
Max. cable cross-section 1.5 mm²
Operating current 100 mA
Ambient Temperature +0 ... +55 °C
Performance level d
Conventional thermal current 5A
Mechanical life (min.) 50,000,000
Allowed type of cable solid single-wire | flexible
Note (Wiring diagram) To secure one or a number of guard doors up to PL c and Category 1 | Monitoring further guard doors: Further magnetic safety sensors can be connected to S2 in a similar way to those on S1. | Monitoring a number of guard doors using magnetic safety sensors BNS range | The wiring diagram is shown with guard doors closed and in de-energised condition.
Terminal connection Screw terminals
Cross-circuit detection Yes
Wire breakage detection Yes
Automatic reset function Yes
Min. Ortam Sıcaklığı +0 °C
Note (Delivery capacity) Not available!
Number of safety contacts 1
Maks. Ortam Sıcaklığı +55 °C
Note (Contact resistance) in new state
Indicated operating states Authorised operation
Overvoltage category III
Contact resistance, maximum 0.1 Ω
Nominal Çalışma Voltajı 24 VDC ± 15 % | 24 VDC
Switching capacity, maximum 250 VAC | 2 A | 24 VDC | 8 A
Switching capacity, minimum 10 VDC | 10 mA
Electrical power consumption 2.5 W
Note (application conditions) Safety sensor | Guard system
Conduction resistance, maximum 40 Ω
Rated impulse withstand voltage (Uimp) 4.8 kV
Depolama / Taşıma Sıcaklığı -25 ... +75 °C | -25 ... +70 °C
Pull-in delay at RESET, typically 20 ms
Current, Utilisation category AC-15 6 A
Current, Utilisation category DC-13 6 A
Integral system diagnostics, status Yes
Voltage, Utilisation category AC-15 230 VAC
Voltage, Utilisation category DC-13 24 VDC
Number of NO (Normally Open) Contacts 2
Rated control voltage at DC, maximum 27.6 VDC
Number of NC (Normally Closed) Contacts 4
IP Degree of protection of the enclosure IP40
Rated control voltage at AC 50 Hz, maximum 26.4 VAC
Rated control voltage at AC 60 Hz, maximum 26.4 VAC
Storage and transport temperature, maximum +70 °C
Storage and transport temperature, minimum -25 °C
Rated AC voltage for controls at DC minimum 20.4 VDC
Reset after disconnection of supply voltage Yes
IP Degree of protection of clips or terminals IP20
Rated AC voltage for controls, 50 Hz, minimum 20.4 VAC
Rated AC voltage for controls, 60 Hz, minimum 20.4 VAC
Drop-out delay in case of emergency, typically 20 ms
IP Degree of protection of the installation space IP54
Drop-out delay in case of power failure, typically 80 ms
Pull-in delay at automatic start, maximum, typically 100 ms
Safety Integrity Level (SIL), suitable for applications in 2

More products in this category

shopping_cart
Quote Cart
shopping_cart

Your cart is empty.

You can add products from product pages.

compare_arrows Compare 0 / 3