Order No
101172211
Article Code
101172211
Schmersal
Emniyetli Sinyal İşleme
Güvenlik İzleme Modülleri
AES2285
Product Description
- • Voltage: 24 VDC | Dimensions: 45mm×100mm×121mm | Weight: 430 g | PL d
Standards
- • EN IEC 60947-5-1 EN IEC 61508
Product Features
- • Multi-evaluation of up to 6 safety guards_x000D_
- • BNS serisi manyetik güvenlik sensörü izleme_x000D_
- • 2 güvenlik kontağı, STOP 0_x000D_
- • 6 Signalling outputs_x000D_
- • Additional contacts by means of output expander_x000D_
- • Individual signal outputs for each guard door
Technical Specifications
Mounting
Fits onto a standard DIN rail per EN 60715
Warning
Discontinued product
Depth
121 mm
Category
3
General Note
Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width
45 mm
Height
100 mm
PFH Value
2.00 x 10⁻⁸ /h
Number of LEDs
3
Impact Resistance
10 g / 11 ms
EMC Class
EMC Directive
Application Note
Safety sensor Guard system
Mission Time
20 Year(s)
Gross Weight
430 g
Housing Material
Glass-fibre reinforced thermoplastic, ventilated
Contact Material
AgCdO, self-cleaning, positive drive
Start Input
Yes
Pollution Degree
2
Min. Cable Cross-Section
0.25 mm²
Vibration Resistance
10 ... 55 Hz, Amplitude 0.35 mm
Electronic Fuse
Yes
Frequency Range
50 Hz 60 Hz
Clip Tightening Torque
0.6 Nm
Max. Cable Cross-Section
2.5 mm²
Terminal (Mechanical)
Threaded terminal block
Climatic Resistance
EN 60068-2-78
Ripple Voltage
0.1
Stop Category
0
Ambient Temperature
-25 ... +45 °C
Performance Level
d
Reset Edge Detection
Yes
Thermal Test Current
0.25
Operating Voltage
24 VAC -15 % / +10 % 24 VDC -15 % / +40 %
Feedback Circuit
Yes
IP Protection (Housing)
IP40
Max. Contact Resistance
0.1 Ω
Mechanical Life (min.)
10,000,000 Cycles
Note (Contact Resistance)
In new condition
Terminal Definitions
IEC/EN 60947-1
Reset When Power is Removed
Yes
Max. Transmission Resistance
40 Ω
Wire Breakage Detection
Yes
Cross-Circuit Detection
Yes
Suitable SIL Applications
3
Connection Diagram Note
K3 and K4 contactor konumu feedback supply circuit with is monitored. Automatic start X1/X3 terminallerine by connecting is programmed. PL d and Category 3'e up to 6 guard door monitoring. Start butonu (S) kenar with detection.
Permissible Cable Type
Single core solid / esnek
Number of Safety Contacts
2
IP Protection (Mounting Area)
IP54
Automatic Reset Function
Yes
Current Utilization Cat. AC-15
0.25
Current Utilization Cat. DC-12
0.1 A
Current Utilization Cat. DC-13
0.25
Number of Auxiliary Contacts
1
Overvoltage Category
III
Electrical Power Consumption
6.6 VA
Min. Switching Capacity
10 mA
Rated Operating Voltage
24 VDC
Number of Signal Outputs
6
AC Control Voltage 50Hz min.
20.4 VAC
AC Control Voltage 60Hz min.
20.4 VAC
Voltage Utilization Cat. AC-15
230 VAC
Voltage Utilization Cat. DC-12
24 VDC
Voltage Utilization Cat. DC-13
24 VDC
IP Protection (Terminal Block)
IP20
Max. Switching Capacity
0.08333333333212067
Earth Connection Detection
Yes
Removable Terminals
Yes
AC Control Voltage 50Hz max.
26.4 VAC
AC Control Voltage 60Hz max.
26.4 VAC
Min. Number of Overlapping Contacts
1
Impulse Withstand Voltage (Uimp)
4 kV
Max. Number of Overlapping Contacts
6
Emergency Release Delay
20 ms
Storage/Transport Temperature
-40 ... +85 °C
Integrated System Diagnostics Status
Yes
Pull-In Delay After RESET
20 ms
Diagnostic Coverage (DC) Level
≥ 99 %
DC Min. Rated Control Voltage
20.4 VDC
Min. Common Cause Failure (CCF)
65
DC Max. Rated Control Voltage
28.8 VDC
Displayed Operating States
Konum relay K2 Konum relay K1 Internal operation voltage U i
Release Delay on Power Failure
80 ms
Pull-In Delay on Automatic Start
100 ms
Number of Undelayed Semiconductor Outputs (with Signal Function)
6