AZR31S1-2SEC./230VAC
Order No 101179105
Schmersal Safe Switching and Monitoring Emniyet Konum Şalterleri (PS Serisi)

AZR31S1-2SEC./230VAC

AZR31S1-2SEC./230VAC — Schmersal product. Key specifications: Housing Material: Glass-fibre, reinforced thermoplastic; Ambient Temperature: -25 ... +45 °C; Depth: 121 mm; Mounting: Snaps onto standard DIN rail to EN 60715; Width: 45 mm. Article number: 101179105. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • Ağırlık: 400 g

Standards

  • • EN IEC 60947-5-3
  • • EN IEC 61508
  • • EN IEC 60947-5-5
  • • EN IEC 60947-5-1
  • • EN IEC 60204-1
  • • EN IEC 60947-1
  • • EN ISO 13849-1
  • • EN IEC 62061

Product Features

  • • Fail-safe standstill monitors
  • • Sensor-free detection of standstill by monitoring e.m.f.
  • • Direct connection to three-phase motors
  • • Suitable for connection to a frequency converter with the following interface date: rotary hysteresis 0 ... 1000 Hz; switching frequency of the end level up to 16 kHz; engine voltage range 0 ... 400 V
  • • This fail-safe standstill monitor has the particular advantage that no adjustment for a required-value is needed during comissioning.
  • • 3 safety contacts, STOP 0
  • • 1 Signalling output

Technical Specifications

Depth 121 mm
Mounting Snaps onto standard DIN rail to EN 60715
General note Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Width 45 mm
PFH value 2.00 x 10⁻⁸ /h
EMC rating EMC-Directive
Height 73.2 mm
Cable Cross-Section 0.25 mm² ... 2.5 mm²
Voltage type AC
Shock resistance 30 g / 11 ms
Stop-Category 0
Mission time 20 Year(s)
Net Ağırlık 400 g
Number of LEDs 5
Bağlantı Tipi rigid or flexible | Screw terminals M20 x 1.5
Climatic stress EN 60068-2-78
Frequency range 50 Hz | 60 Hz
Gross weight 400 g
Category, Stop 0 4
Feedback circuit Yes
Housing Material Glass-fibre, reinforced thermoplastic
Contact material AgSn0. self-cleaning, positive drive
Pollution degree 2
Min. cable cross-section 0.25 mm²
Operating voltage 230 VAC -15 % / +10 %
Vibration resistance 10 ... 55 Hz, Amplitude 0.35 mm
Max. cable cross-section 2.5 mm²
Ambient Temperature -25 ... +45 °C
Mechanical life (min.) 10,000,000
Note (Wiring diagram) After release has taken place, the guard door must be opened. | Monitoring the guard door using a solenoid interlock and a safety switch with separate actuator (A and B). | Release takes place by means of the NO contact (E) only when the run-down movement has been terminated. | The SRB range guard door monitor checks the position of the guard door. | To secure a guard door | The sensor-free standstill monitor checks the e.m.f. of the three phase motor. | The wiring diagram is shown with guard doors closed and in de-energised condition.
Terminal designations IEC/EN 60947-1
Cross-circuit detection Yes
Wire breakage detection Yes
Automatic reset function Yes
Min. Ortam Sıcaklığı -25 °C
Note (Delivery capacity) Not available!
Number of safety contacts 3
Maks. Ortam Sıcaklığı +45 °C
Note (Contact resistance) in new state
Earth connection detection Yes
Indicated operating states OUT, green: release | ON, green: supply voltage UB | ERR, red: error channel A + B
Tightening torque of Clips 0.6 Nm
Utilisation category DC-12 24_0.1
Number of auxiliary contacts 1
Overvoltage category III
Contact resistance, maximum 0.1 Ω
Nominal Çalışma Voltajı 230 VAC | 230 VAC -15% / +10%
Switching capacity, maximum 250 VAC | 2 A | 24 VDC | 8 A
Switching capacity, minimum 10 VDC | 10 mA
Note (application conditions) safe standstill monitoring
Conduction resistance, maximum 40 Ω
Rated impulse withstand voltage (Uimp) 4 kV
Performance Level, stop 0, up to e
Depolama / Taşıma Sıcaklığı -40 ... +85 °C
Pull-in delay at RESET, typically 20 ms
Common Cause Failure (CCF), minimum 65
Current, Utilisation category AC-15 6 A
Current, Utilisation category DC-12 0.1 A
Current, Utilisation category DC-13 6 A
Integral system diagnostics, status Yes
Voltage, Utilisation category AC-15 230 VAC
Voltage, Utilisation category DC-12 24 VDC
Voltage, Utilisation category DC-13 24 VDC
Cable length (Master/Slave), maximum 10 m
Electrical power consumption, maximum 4 VA
Diagnostic Coverage (DC) Level, Stop 0 ≥ 99 %
IP Degree of protection of the enclosure IP40
Rated control voltage at AC 50 Hz, maximum 253 VAC
Rated control voltage at AC 60 Hz, maximum 253 VAC
Storage and transport temperature, maximum +85 °C
Storage and transport temperature, minimum -40 °C
IP Degree of protection of clips or terminals IP20
Rated AC voltage for controls, 50 Hz, minimum 195.5 VAC
Rated AC voltage for controls, 60 Hz, minimum 195.5 VAC
Drop-out delay in case of emergency, typically 20 ms
IP Degree of protection of the installation space IP54
Drop-out delay in case of power failure, typically 80 ms
Drop-out delay in case of "emergency stop", maximum 15 ms
Safety Integrity Level (SIL), Stop 0, suitable for applications in 3
Pull-in delay at automatic start (after detecting standstill), approx. 2,000 ms

More products in this category

shopping_cart
Quote Cart
shopping_cart