Order No
103027190
Article Code
103027190
Certificates
cULus
Schmersal
Emniyetli Anahtarlama ve Denetleme
Emniyet Sensörleri
BNS 260-02Z-ST-L-2750
Product Description
- • IP Rating: IP67 | Weight: 43 g | Certification: cULus | Contacts: 2 NC
Standards
- • EN ISO 13849-1
Product Features
- • Termoplastik gövde_x000D_
- • Kompakt gövde_x000D_
- • Gizli montaj mümkün_x000D_
- • 26 mm x 36 mm x 13 mm_x000D_
- • Uzun ömürlü_x000D_
- • Mekanik aşınma yok_x000D_
- • Yanal hizasızlığa karşı duyarsız_x000D_
- • Kirlenmeye karşı duyarsız
Technical Specifications
Coding
Yes
General Note
Contact sembolleri, guard of the device closed condition for is shown. LED'li or LED'siz of the versions contact configuration is the same.
Impact Resistance
30 g / 11 ms
Mission Time
20 Year(s)
Direction of Movement
Active to the surface vertical
Gross Weight
43 g
Housing Material
Cam elyaf takviyeli termoplastik
Sensor Length
13 mm
Scope of Delivery
Actuator additionally order must be.
Vibration Resistance
10 … 55 Hz, amplitude 1 mm
Actuation Element
Magnet
IP Protection Class
IP67
Ambient Temperature
-25 ... +70 °C
Sensor Width
26 mm
Operating Principle
Magnetic drive
Switching Element
2 NK contact
Sensor Height
36 mm
Recommendation (Actuator)
BPS 260
B10D NC Contact Value
25,000,000 Cycles
Terminal Connection
Connector M8, 4-pole, A-coded
Connection Diagram Note
S11-S12 and S21-S22 contacts safety devresine integrated must be.
B10D NC/NA Contact Value
25,000,000 Cycles
Number of Safety Contacts
2
Max. Switching Current
0.4 A
Max. Switching Voltage
30 VDC
Mechanical Mounting Conditions
Semi-recessed
Note (Switching Distance)
All switching distances EN IEC 60947-5-3'e is according to
Electrical Connection Torque
0.3 Nm
Max. Switching Capacity
10 VA
Guaranteed Opening Distance (ON) Sao
8 mm
Note (Switching Distance Sn)
Axial misalignment: horizontal and vertical misalignment between the safety sensor and the actuator is tolerated. The possible misalignment depends on the distance between the active surfaces of the sensor and the actuator. The sensor remains active within the tolerance range.
Impulse Withstand Voltage (Uimp)
0.8 kV
Guaranteed Opening Distance (OFF) Sar
18 mm
Storage/Transport Temperature
-25 ... +70 °C
Coding Level (EN ISO 14119)
Low
Recommended Safety Switch
SRB-E-301ST SRB-E-201LC
Rated Insulation Voltage (Uᵢ)
50 VAC 75 VDC
Max. Switching Frequency (Approx.)
5 Hz
Required Rated Short-Circuit Current
100 A
Number of NC (Normally Closed) Contacts
2