EX-BS655-T22 — Schmersal product. Key specifications: Switching principle: Slow action; Switching element: 2 NO contact, 2 NC contacts; Housing Material: Grey cast iron, painted; IP protection class: IP66 | IP67; Ambient Temperature: -25 ... +70 °C | -40 ... +100 °C. Article number: 153045274. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • IP: IP67
  • • Ağırlık: 6,005 g
  • • Sertifika: ATEX, IECEx, NEPSI, CCC-EX ATEX IECEx

Standards

  • • EN IEC 60947-5-1
  • • EN ISO 13849-1

Product Features

  • • Ex-Zone 1 and 21
  • • Metal enclosure
  • • Protection class IP66, IP67
  • • Platform concept with different function units
  • • Lever angle adjustable in 10° steps

Technical Specifications

Cable Cross-Section 0.75 mm² ... 2.5 mm² (All indications including the conductor ferrules.) | 0.5 mm² ... 2.5 mm²
Cable entry 2 x M25 x 1.5
Mission time 20 Year(s)
Net Ağırlık 6,005 g
Bağlantı Tipi Screw terminals
Gross weight 6,005 g
Housing Material Grey cast iron, painted
Contact material Silver
Protection class I
Safety functions Yes
Pollution degree 3
Min. cable cross-section 0.75 mm²
Max. cable cross-section 2.5 mm²
IP protection class IP66 | IP67
Ambient Temperature -25 ... +70 °C | -40 ... +100 °C
Conventional thermal current 6 A
Switching element 2 NO contact, 2 NC contacts
Switching principle Slow action
Mechanical life (min.) 1,000,000
Utilisation category AC-15 | DC-13
Min. Ortam Sıcaklığı -25 °C
Number of safety contacts 2
Maks. Ortam Sıcaklığı +65 °C
Explosion protection zones 21 | 1
Utilization Category AC-15 3 A | 230 VAC
Utilization Category DC-13 24 VDC / 3 A | 3 A | 24 VDC
Number of auxiliary contacts 2
Explosion protection category 2G | 2D
Material of the housing cover Grey cast iron, painted
Rated impulse withstand voltage (Uimp) 4 kV
Explosion protection designation D II 2D Ex tb IIIC T85°C Db | D II 2G Ex d e IIC T6 Gb
B10D Normally-closed contact (NC) 1,000,000
Explosion protection: regulations EN IEC 60079-0 | EN 60079-11 | EN 60079-7 | EN 60079-31 | EN 60079-1
Rated insulation voltage (Uᵢ) 300 V
Protection class (Operating resource) 1