PS116-T11-L200-N200
Order No 103047776
Certificates cULus, CCC
Schmersal Safe Switching and Monitoring Emniyet Konum Şalterleri (PS Serisi)

PS116-T11-L200-N200

PS116-T11-L200-N200 — Schmersal product. Key specifications: Switching principle: Slow action; Switching element: 1 NO contact, 1 NC contacts; IP protection class: IP66 | IP67; Ambient Temperature: -30 ... +80 °C; Terminal connection: bottom. Article number: 103047776. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • IP: IP67
  • • Ağırlık: 236 g
  • • Sertifika: cULus, CCC

Standards

  • • EN IEC 60947-5-1
  • • EN ISO 13849-1

Product Features

  • • Pre-wired cable bottom, 2
  • • Thermoplastic enclosure
  • • With plastic roller
  • • length adjustable in 2 mm steps
  • • Lever angle adjustable in 15° steps
  • • Actuator heads can be repositioned by 8 x 45°

Technical Specifications

Note at 10% Ie and ohmic load
CADENAS Yes
Cable type LiYY
Traceparts Yes
Active area Metal film
Mission time 20 Year(s)
Net Ağırlık 236 g
Bağlantı Tipi Pre-wired cable | Cable, 4-pole
Length of cable 2 m
Gross weight 236 g
Housing Material Plastic, glass-fibre reinforced thermoplastic, zinc die-cast, chromated
Contact material Silver
Protection class II
Safety functions Yes
Pollution degree 3
Sensor length 16.6 mm
Diameter of Castor 20 mm
Cylinder Material Plastic
Wire cross-section 0.5 mm²
Actuation Element Roller lever N200
IP protection class IP66 | IP67
Ambient Temperature -30 ... +80 °C
Sensor width 31 mm
Switching element 1 NO contact, 1 NC contacts
Switching principle Slow action
Mechanical life (min.) 10,000,000
Sensor height 139 mm
Number of cable wires 4
Positive break torque 0.6 Nm
Min. Actuation Speed 60 mm/min
Terminal connection bottom
Max. actuating speed 1 m/s
Bounce duration, maximum 3 ms
Min. Ortam Sıcaklığı -30 °C
Switchover time, maximum 5.5 ms
Actuating torque, minimum 0.2 Nm
Actuator type to EN 50047 A
Number of safety contacts 1 | 1 / 2
Housing construction form Norm construction design
Maks. Ortam Sıcaklığı +80 °C
Utilization Category AC-15 240 VAC
Utilization Category DC-13 24 VDC | 1.5 A | 24 VDC / 1.5 A
Number of auxiliary contacts 1 / 2 | 1
Max. switching frequency 5,000 /h
Positive break force, minimum 40 N
Rated impulse withstand voltage (Uimp) 4 kV
B10D Normally-open contact (NO) 1,000,000
B10D Normally-closed contact (NC) 20,000,000
Rated insulation voltage (Uᵢ) 300 V
Required rated short-circuit current 400A

More products in this category

shopping_cart
Quote Cart
shopping_cart

Your cart is empty.

You can add products from product pages.