Order No
101214772
Certificates
TÜV cULus ECOLAB FCC IC ANATEL
Schmersal
System Solutions
Series Diagnostic Systems
RSS 36-SD-ST Series Diagnostic Systems
Schmersal RSS 36-SD-ST features RFID working principle, cam elyaf takviyeli termoplastik housing material, IP65 IP67 IP69 protection class and -28 ... +70 °C ambient temperature.
Product Description
- • IP Rating: IP65/IP67/IP69
- • Voltage: 24 VDC
- • Weight: 85 g
- • PL e
Standards
- • EN ISO 13849-1
- • EN IEC 61508
Product Features
- • Universal coding with RFID technology
- • 1 x connector socket M12, 8-pole
- • Actuation from the side
- • Max. 31 sensors can be wired in series.
- • serial diagnostic output
- • Thermoplastic housing
- • RFID technology for demand-based tamper protection
- • Misaligned actuation possible
- • 27 mm x 108.2 mm x 35 mm
- • High repeat accuracy of the switching points
- • 2 short-circuit proof PNP safety outputs
- • Integral cross-short, wire-breakage and external voltage monitoring of the safety cables up to the control cabinet
Technical Specifications
PIN 1
1A1 Ue: (1)
PIN 2
X1 Safety input 1
PIN 3
A2 GND Blue
PIN 4
Y1 Safety output 1 Black
PIN 5
OUT serial diagnostic output: grey
PIN 6
X2 Safety input 2 violet
PIN 7
Y2 Safety output 2 red
PIN 8
INPUT serial diagnostic input Pink
Mounting
A screw length of 25 mm is sufficient for mounting the sensor and for lateral mounting of the actuators. If the actuator is mounted vertically and/or sealing discs are used, 30 mm long screws are recommended.
Coding
Universal coding
Category
4
General note
Evaluation requirements: two-channel safety input, suitable for p-switching sensors with NO function.
Active Area
Lateral
PFD Value
2.10 x 10⁻⁵
PFH value
2.70 x 10⁻¹⁰ /h
Number of LEDs
3
Shock resistance
30 g / 11 ms
Mission time
20 Year(s)
Max. Hysteresis
2 mm
Serial Diagnostics
Yes
Series Connection
Yes
Gross weight
85 g
Housing Material
Glass-fibre reinforced thermoplastic
Protection Class
III
Pollution degree
3
Max. Relative Humidity
93 %
Note (Relative Humidity)
Non-condensing, non-icing
Radiated Interference
IEC 61000-6-4
Sensor length
22 mm
Scope of delivery
Actuator must be ordered separately.
Vibration resistance
10 … 55 Hz, amplitude 1 mm
Cable Capacitance
50 nF
Max. Risk Time
200 ms
Sensor Topology
Sensor for series connection
Operating current
150 mA
IP protection class
IP65 IP67 IP69
Short-Circuit Detection
Yes
Max. reaction time
100 ms
Ambient Temperature
-28 ... +70 °C
Performance level
e
RFID Frequency Band
125 kHz
Sensor width
106.3 mm
Operating voltage
24 VDC -15% / +10% (stabilised PELV power supply)
Working Principle
RFID
Actuation Panels
Lateral
Cascadable
Yes
Mechanical life (min.)
1,000,000 Cycles
Housing Design
Block
Note (Mechanical Life)
Actuating speed < 0.25 m/s, operating cycles for door weights ≤ 5 kg
Sensor height
25 mm
Recommendation (Actuator)
RST 36-1 RST 36-1-R
Repeat Accuracy R
0.5 mm
Note (Series Connection)
Unlimited number of devices; observe the external line fuse; max. 31 devices when using serial diagnostics (SD)
Cross-Circuit Detection
Yes
Fixing screw type
2x M4 (cheese-head screws with DIN 125A / form A washers)
Terminal connection
Connector M12, 8-pole
Max. Leakage Current (Ir)
0.5 mA
Min. Operating Current
0.5 mA
Suitable SIL Applications
3
Safety Functions
Yes
Max. installation altitude
2,000 m
Max. Test Pulse Duration
0.3 ms
Max. Ready Time
2,000 ms
Current Utilization Cat. DC-12
0.25 A
Current Utilization Cat. DC-13
0.25 A
Mechanical Mounting Conditions
Non-flush
Min. Test Pulse Interval
100 ms
Note (Switching Distance)
All switching distances according to EN IEC 60947-5-3
Note (Repeat Accuracy R)
Axial offset: the long edge allows a maximum height misalignment (x) of 8 mm between the sensor and the actuator. Axial misalignment (y) max. ±18 mm. Minimum distance of 100 mm between two sensor systems.
Typical Switching Distance
12 mm
Overvoltage category
III
Rated operating voltage
24 VDC
Typical Test Pulse Interval
1000 ms
Voltage Utilization Cat. DC-12
24 VDC
Voltage Utilization Cat. DC-13
24 VDC
Min. Fixing Screw Torque
2.2 Nm
Serial Diagnostics (SD) Definition
OUT
Assured Switch-On Distance Sao
10 mm
Safety Inputs Definition
X1 and X2
Max. Voltage Drop (Ud)
1 V
Max. Fixing Screw Torque
2.5 Nm
Max. Transmitter RFID Output
-6 dBm
Number of Sensors Connected in Series
31
Rated impulse withstand voltage (Uimp)
0.8 kV
Assured Switch-Off Distance Sar
20 mm
Control Elements Design
Short-circuit proof, p-type
Storage/transport temperature
-28 ... +85 °C
Integrated System Diagnostics Status
Yes
Coding level (EN ISO 14119)
Low
Note (Sensor Chain Length)
Cable length and cross-section change the voltage drop depending on the output current
Recommended Safety Switch
PROTECT PSC1 SRB-E-301ST SRB-E-201LC
Safety Outputs Definition
Y1 and Y2
Max. Electrical Fuse Rating
2 A
Rated insulation voltage (Uᵢ)
32 VDC
Max. Switching Frequency (Approx.)
1 Hz
Required rated short-circuit current
100A
Number of Safe Digital Outputs
2
ZVEI CB24I Sink Classification
C1 C2
Safety Inputs Current Consumption
5 mA
ZVEI CB24I Source Classification
C2
Typical Idle Operating Current (I₀)
35 mA
Max. Output Current (Safe Output)
0.25 A
Note (LED Switching Condition Indication)
Yellow LED: operating status Green LED: supply voltage Red LED: fault
Number of Semiconductor Outputs with Signal Function
1
Rated Operating Current (Safety Outputs)
250 mA
Max. Response Time (Actuator to Safety Output Off)
100 ms
Max. Response Time (Safety Input to Safety Output Off)
0.5 ms