RSS260-I2-ST-AS-DU
Order No 103045605
Certificates cULus TÜV TÜV, cULus, ASi-SaW, FCC, ANATEL FCC ASi-SaW
Schmersal Safe Switching and Monitoring Emniyet Konum Şalterleri (PS Serisi)

RSS260-I2-ST-AS-DU

RSS260-I2-ST-AS-DU — Schmersal product. Key specifications: Working Principle: RFID; Housing Material: Glass-fibre, thermoplastic; IP protection class: IP67 | IP65; Ambient Temperature: -25 ... +60 °C | -30 ... +60 °C; Terminal connection: Connector plug M8, 4-pole, A-coded. Article number: 103045605. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • IP: IP65
  • • Ağırlık: 55 g
  • • Sertifika: cULus TÜV TÜV, cULus, ASi-SaW, FCC, ANATEL FCC ASi-SaW

Standards

  • • EN 61508
  • • EN IEC 62026-2
  • • EN ISO 13849-1
  • • EN ISO 14119
  • • EN IEC 60947-5-3
  • • EN IEC 61508
  • • EN 62026-2
  • • EN 60947-5-3

Product Features

  • • Repeated individual coding with RFID technology
  • • Coding level "High" according to ISO 14119
  • • Safety sensor, electronic
  • • Thermoplastic enclosure
  • • Small body, high switching distance
  • • Protection class IP65 / IP67

Technical Specifications

PIN 1 AS-Interface +
PIN 2 n.c. (≤ 30 VDC)
PIN 3 AS-Interface -
PIN 4 n.c. (≤ 30 VDC)
Coding Individual coding, multiple teaching
Category 4
PFD value 6.89 x 10⁻⁵
PFH value 3.93 x 10⁻¹⁰ /h
LED colour green/red (AS-i Duo LED) | Yellow
LED status supply voltagecommunication errorslave address = 0periphery error detectedtamper protection time active | device condition (enabling status)hysteresis signaldevice error
Note (Sao) The specifications of the safety switching distance Sao refer to a temperature range of -10 °C ... +60 °C. For a temperature range of -25 °C ... +60 °C, Sao is reduced by 2 mm.
Active area Glass-fibre, thermoplastic
AS-i Profile S-0.B.F.E
AS-i Version V 3.0
AS-i, ID-Code 0xB
AS-i, IO-Code 0x0
Shock resistance 30 g / 11 ms
AS-i, ID-Code1 0xF
AS-i, ID-Code2 0xE
Mission time 20 Year(s)
Net Ağırlık 55 g
Number of poles 4
Gross weight 55 g
Housing Material Glass-fibre, thermoplastic
Protection class III
Safety functions Yes
Pollution degree 3
Repeat accuracy R 0.5 mm
Scope of delivery Actuator must be ordered separately.
Sensor length 18 mm
Vibration resistance 10 … 55 Hz, amplitude 1 mm
AS-i Specification Safety-Slave
Frequency band RFID 125 kHz
IP protection class IP67 | IP65
Ambient Temperature -25 ... +60 °C | -30 ... +60 °C
Performance level e
Sensor width 40 mm
Working Principle RFID
Sensor height 29.5 mm
AS-i Input, Channel 1 Data bits DI 0 / DI 1 = dynamic code transmission
AS-i Input, Channel 2 Data bits DI 2 / DI 3 = dynamic code transmission
Switching distance Sn 12 mm | 9 mm (in case of approach from side)
AS-i Device protection Internal short-circuit proof
Terminal connection Connector plug M8, 4-pole, A-coded
AS-i Parameter bits, P0 Actuator in
AS-i Parameter bits, P1 Enabling inhibit (tamper protection time) active (FID))
AS-i Parameter bits, P2 Enabling inhibit (tamper protection time) active (FID)
AS-i Parameter bits, P3 Internal device error (FID)
Min. Ortam Sıcaklığı -25 °C
Note (Delivery capacity) Not available!
Note (Relative humidity) non-condensing | non-icing
AS-i Input module address 0
Duration of risk, maximum 200 ms
Maks. Ortam Sıcaklığı +60 °C
Note (switching distance) All switching distances in accordance EN IEC 60947-5-3
Recommendation (actuator) RST260-1
Relative humidity, maximum 93 %
Time to readiness, maximum 2,000 ms
AS-i Outputs, DO 0 … DO 3 No Function
Overvoltage category 3 | III
Nominal Çalışma Voltajı 18 ... 31.6 VDC (Protection against polarity reversal)
Note (AS-i Parameter bits) Set the parameter outputs to "1111" (0xF) | FID: periphery error
Switching frequency, maximum 1 Hz
Note (AS-i Operating voltage) Protection against polarity reversal
AS-i Parameter bits, P0 ... P3 Actuator number 0Actuator number 01 - 15
Rated impulse withstand voltage (Uimp) 0.8 kV
Number of actuating directions 2
AS-i Operating voltage, minimum 18 VDC
Note (AS-i Input module address) Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Transmitter output RFID, maximum -6 dBm
AS-i Current consumption, maximum 100 mA
Depolama / Taşıma Sıcaklığı -25 ... +85 °C | -40 ... +85 °C
Rated insulation voltage (Uᵢ) 32 VDC
AS-i Operating voltage AS-i maximum 31.6 VDC
Typical switching distance, frontal 12 mm
Typical switching distance, lateral 9 mm
Integral system diagnostics, general Yes
Protection class (Operating resource) 3
Coding level according to EN ISO 14119 High
Assured switching distance "ON", frontal 10 mm
Assured switching distance "ON", lateral 6 mm
Hysteresis (Switching distance), maximum 2 mm
Assured switching distance "OFF", frontal 18 mm
Assured switching distance "OFF", lateral 15 mm
Note (scope of delivery, number and type) Actuator incl. mounting plate
Storage and transport temperature, maximum +85 °C
Storage and transport temperature, minimum -25 °C
Permissible installation altitude above sea level, maximum 2,000 m
Safety Integrity Level (SIL), suitable for applications in 3
Reaction time, switching off safety outputs via actuator, maximum 140 ms

More products in this category

shopping_cart
Quote Cart
shopping_cart

Your cart is empty.

You can add products from product pages.

compare_arrows Compare 0 / 3