Order No
101192805
Article Code
101192805
Schmersal
Aksesuar ve Bağlantı Elemanları
Ağ Geçitleri ve İletişim
SD-I-DP-V0-2 PROFIBUS-GATEWAY
Product Description
- • Voltage: 24 VDC | Dimensions: 50mm×72mm×97mm | Weight: 120 g
Product Features
- • PROFIBUS Gateway SD-I-DP-V0-2 to convert serial diagnostic signals to the PROFIBUS DP protocol_x000D_
- • The PROFIBUS Gateway SD-I-DP-V0-2 is a PROFIBUS slave_x000D_
- • Protection class IP 10 device for control cabinet mounting, for standard DIN rails
Technical Specifications
Mounting
Fits onto a standard DIN rail per EN 60715
Depth
97 mm
General Note
Detailed fonksiyonlar for SD Gateway programlama and configuration to the guide see
Width
50 mm
Height
72 mm
Number of LEDs
4
Impact Resistance
15 g / 11 ms
Application Note
Safety sensor Guard system
Gross Weight
120 g
Pollution Degree
2
Vibration Resistance
5 ... 9 Hz, Amplitude 3,5 mm 9 ... 150 Hz, 1 g with
Operating Current
250 mA
Ambient Temperature
-5 ... +55 °C
Operating Voltage
24 VDC -15 % / +20 %
IP Protection (Housing)
IP10
Terminal Connection
Cage clamps
Connection Diagram Note
Serial diagnostics of series-connected safety sensors/solenoid locks. Devices with a serial diagnostics option: AZ 200, AZM 200, CSS 30S, CSS 34, MZM 100
Overvoltage Category
II
Rated Operating Voltage
24 VDC
Impulse Withstand Voltage (Uimp)
0.5 kV
Storage/Transport Temperature
-25 ... +85 °C
Integrated System Diagnostics Status
Yes
Rated Insulation Voltage (Uᵢ)
32 V
Note (LED Switching Condition Indication)
OPEN continuous green light: supply voltage available PB Flashing fading sinyal: PROFIBUS start PB Continuous red light: PROFIBUS error SD Flashing fading sinyal: = SD network gateway start SD Continuous red light: = SD Network gateway...