Order No
103014308
Article Code
103014308
Certificates
TÜV cULus
Schmersal
Emniyetli Sinyal İşleme
Güvenlik İzleme Modülleri
SRB-E-232ST
Product Description
- • Voltage: 24 VDC | Dimensions: 22.5mm×98mm×115mm | Weight: 170 g | Contacts: 2 NC, 1 NO | PL e
Standards
- • EN ISO 13849-1 EN IEC 62061 EN IEC 61508
Product Features
- • Plug-in screw terminals with coding_x000D_
- • STOP 0 / 1 Function_x000D_
- • 1 oder 2-channel control_x000D_
- • 2 Safety outputs STOP 0_x000D_
- • 3 safety contacts STOP 1_x000D_
- • Drop-out delay adjustable in steps 0 … 30
Technical Specifications
Mounting
Fits onto a standard DIN rail per EN 60715
Depth
115 mm
Category
4
Width
22.5 mm
Height
98 mm
PFD Value
2.42 x 10⁻⁵
PFH Value
2.66 x 10⁻⁹ /h
Number of LEDs
6
Impact Resistance
30 g / 11 ms
EMC Class
EMC Directive
Application Note
Safety sensor Protection system hinged guard door Acil stopping butonu Pull wire acil stopping switch Safety light curtain Safety light bariyerleri
Mission Time
20 Year(s)
Gross Weight
170 g
Housing Material
Glass-fibre reinforced thermoplastic, ventilated
Contact Material
Ag-Ni, self-cleaning, positive drive
Start Input
Yes
Pollution Degree
2
Min. Cable Cross-Section
0.25 mm²
Vibration Resistance
10 ... 55 Hz, Amplitude 0.35 mm
Clip Tightening Torque
0.5 Nm
Max. Cable Cross-Section
2.5 mm²
Terminal (Mechanical)
Removable threaded terminaller
Ripple Voltage
0.1
Stop Category
0 1
Ambient Temperature
-25 ... +60 °C
Performance Level
e
Reset Edge Detection
Yes
Operating Voltage
24 VDC -20% / +20% (PELV power unit I maks. 1,0 A, EN 60204'e according to (power interruption ≤ 20 ms))
Feedback Circuit
Yes
IP Protection (Housing)
IP40
Max. Contact Resistance
0.1 Ω
Mechanical Life (min.)
10,000,000 Cycles
Note (Contact Resistance)
In new condition
Terminal Definitions
IEC/EN 60947-1
Max. Transmission Resistance
40 Ω
Wire Breakage Detection
Yes
Cross-Circuit Detection
Yes
Max. Leakage Current (Ir)
1 mA
Suitable SIL Applications
3
Permissible Cable Type
Single core solid / esnek
IP Protection (Mounting Area)
IP54
Automatic Reset Function
Yes
Current Utilization Cat. AC-15
0.16666666666787933
Current Utilization Cat. DC-12
0.1 A
Current Utilization Cat. DC-13
0.16666666666787933
Number of Auxiliary Contacts
1
Overvoltage Category
III
Electrical Power Consumption
3 W
Min. Switching Capacity
10 mA
Rated Operating Voltage
24 VDC
Number of Signal Outputs
1
Voltage Utilization Cat. AC-15
230 VAC
Voltage Utilization Cat. DC-12
24 VDC
Voltage Utilization Cat. DC-13
24 VDC
IP Protection (Terminal Block)
IP20
Max. Switching Capacity
0.041666666667879326
Earth Connection Detection
Yes
Removable Terminals
Yes
Max. Voltage Drop (Ud)
0.5 V
Emergency Release Delay
10 ms
Storage/Transport Temperature
-40 ... +85 °C
Integrated System Diagnostics Status
Yes
Pull-In Delay After RESET
150 ms
Diagnostic Coverage (DC) Level
> 94 %
DC Min. Rated Control Voltage
19.2 VDC
Number of Safety Contacts STOP 1
3
Min. Common Cause Failure (CCF)
65
DC Max. Rated Control Voltage
28.8 VDC
Displayed Operating States
Internal operating voltage Ui, module status, error codes
Integrated System Diagnostics Error Code
Yes
Max. Switching Frequency (Approx.)
0.3 Hz
Number of NO (Normally Open) Contacts
1
Release Delay on Power Failure
10 ms
Number of NC (Normally Closed) Contacts
2
Pull-In Delay on Automatic Start
150 ms
Number of Safe Digital Outputs Stop 0
2
Relay Output Impulse Withstand Voltage (Uimp)
4 kV
Semiconductor Output Impulse Withstand Voltage (Uimp)
0.8 kV