Order No
103014308
Certificates
TÜV cULus
Schmersal
Safe Signal Processing
Security Relay and Control Modules
SRB-E-232ST Security Relay and Control Modules
Schmersal SRB-E-232ST features -25 ... +60 °C ambient temperature, 115 mm depth and 22.5 mm width.
Product Description
- • Voltage: 24 VDC
- • Dimensions: 22.5mm×98mm×115mm
- • Weight: 170 g
- • Contacts: 2 NC, 1 NO
- • PL e
Standards
- • EN ISO 13849-1
- • EN IEC 62061
- • EN IEC 61508
Product Features
- • Plug-in screw terminals with coding
- • STOP 0 / 1 Function
- • 1 oder 2-channel control
- • 2 Safety outputs STOP 0
- • 3 safety contacts STOP 1
- • Drop-out delay adjustable in steps 0 … 30
Technical Specifications
Mounting
Fits onto a standard DIN rail per EN 60715
Depth
115 mm
Category
4
Width
22.5 mm
Height
98 mm
PFD Value
2.42 x 10⁻⁵
PFH value
2.66 x 10⁻⁹ /h
Number of LEDs
6
Shock resistance
30 g / 11 ms
EMC Class
EMC Directive
Application Note
Safety sensor, guard system, hinged guard door, emergency stop button, pull-wire emergency stop switches, safety light curtain, safety light barriers
Mission time
20 Year(s)
Gross weight
170 g
Housing Material
Glass-fibre reinforced thermoplastic, ventilated
Contact material
Ag-Ni, self-cleaning, positive drive
Start Input
Yes
Pollution degree
2
Min. cable cross-section
0.25 mm²
Vibration resistance
10 ... 55 Hz, Amplitude 0.35 mm
Clip Tightening Torque
0.5 Nm
Max. cable cross-section
2.5 mm²
Terminal (Mechanical)
Removable screw terminals
Ripple Voltage
10 %
Stop Category
0 1
Ambient Temperature
-25 ... +60 °C
Performance level
e
Reset Edge Detection
Yes
Operating voltage
24 VDC -20% / +20% (PELV power supply unit, I max. 1,0 A, according to EN 60204 (power interruption ≤ 20 ms))
Feedback Circuit
Yes
IP Protection (Housing)
IP40
Max. Contact Resistance
0.1 Ω
Mechanical life (min.)
10,000,000 Cycles
Note (Contact Resistance)
In new condition
Terminal Definitions
IEC/EN 60947-1
Max. Transmission Resistance
40 Ω
Wire Breakage Detection
Yes
Cross-Circuit Detection
Yes
Max. Leakage Current (Ir)
1 mA
Suitable SIL Applications
3
Permitted cable type
Single-core rigid / flexible
IP Protection (Mounting Area)
IP54
Automatic Reset Function
Yes
Current Utilization Cat. AC-15
4 A
Current Utilization Cat. DC-12
0.1 A
Current Utilization Cat. DC-13
4 A
Number of auxiliary contacts
1
Overvoltage category
III
Electrical Power Consumption
3 W
Min. Switching Capacity
10 mA
Rated operating voltage
24 VDC
Number of Signal Outputs
1
Voltage Utilization Cat. AC-15
230 VAC
Voltage Utilization Cat. DC-12
24 VDC
Voltage Utilization Cat. DC-13
24 VDC
IP Protection (Terminal Block)
IP20
Max. Switching Capacity
1 A
Earth Connection Detection
Yes
Removable Terminals
Yes
Max. Voltage Drop (Ud)
0.5 V
Emergency Release Delay
10 ms
Storage/transport temperature
-40 ... +85 °C
Integrated System Diagnostics Status
Yes
Pull-In Delay After RESET
150 ms
Diagnostic Coverage (DC) Level
> 94 %
DC Min. Rated Control Voltage
19.2 VDC
Number of Safety Contacts STOP 1
3
Min. Common Cause Failure (CCF)
65
DC Max. Rated Control Voltage
28.8 VDC
Displayed Operating States
Internal operating voltage Ui, module status, error codes
Integrated System Diagnostics Error Code
Yes
Max. Switching Frequency (Approx.)
0.3 Hz
Number of NO (Normally Open) Contacts
1
Release Delay on Power Failure
10 ms
Number of NC (Normally Closed) Contacts
2
Pull-In Delay on Automatic Start
150 ms
Number of Safe Digital Outputs Stop 0
2
Relay Output Impulse Withstand Voltage (Uimp)
4 kV
Semiconductor Output Impulse Withstand Voltage (Uimp)
0.8 kV