Order No
101186279
Article Code
101186279
Schmersal
Emniyetli Sinyal İşleme
Güvenlik İzleme Modülleri
SRB100DR
Product Description
- • Voltage: 24 VDC | Dimensions: 22.5mm×100mm×121mm | Weight: 250 g | Contacts: 2 NC
Standards
- • EN IEC 60947-5-1 EN IEC 61508
Product Features
- • Safety relay module for double reset_x000D_
- • Suitable for signal processing of potential-free outputs, e.g. command devices_x000D_
- • 1 güvenlik kontağı, STOP 0
Technical Specifications
Mounting
Fits onto a standard DIN rail per EN 60715
Depth
121 mm
General Note
Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width
22.5 mm
Height
100 mm
Number of LEDs
4
Impact Resistance
30 g / 11 ms
EMC Class
EMC Directive
Mission Time
20 Year(s)
Gross Weight
250 g
Housing Material
Glass-fibre reinforced thermoplastic, ventilated
Contact Material
Ag-Ni, self-cleaning, positive drive
Start Input
Yes
Pollution Degree
2
Min. Cable Cross-Section
0.25 mm²
Vibration Resistance
10...55 Hz, Amplitude 0.35 mm, ± 15 %
Electronic Fuse
Yes
Frequency Range
50 Hz 60 Hz
Clip Tightening Torque
0.6 Nm
Max. Cable Cross-Section
2.5 mm²
PFH Value Stop 0
2.00 x 10⁻⁸ /h
Terminal (Mechanical)
Threaded terminal block
Climatic Resistance
EN 60068-2-78
Ripple Voltage
0.1
Ambient Temperature
-25 ... +60 °C
Operating Voltage
24 VAC -15 % / +10 % 24 VDC -15 % / +20 %
IP Protection (Housing)
IP40
Max. Contact Resistance
0.1 Ω
Mechanical Life (min.)
10,000,000 Cycles
Note (Contact Resistance)
In new condition
Terminal Definitions
IEC/EN 60947-1
Reset When Power is Removed
Yes
Max. Transmission Resistance
40 Ω
Wire Breakage Detection
Yes
Connection Diagram Note
Connection diagram, guard door closed and enerji cut off in the state is shown. Applications: Rotary Kam Switch such as products for.
Permissible Cable Type
Single core solid / esnek
Number of Safety Contacts
1
IP Protection (Mounting Area)
IP54
Current Utilization Cat. AC-15
0.25
Current Utilization Cat. DC-13
0.25
Overvoltage Category
III
Electrical Power Consumption
6 VA
Min. Switching Capacity
10 mA
Rated Operating Voltage
24 VDC
AC Control Voltage 50Hz min.
20.4 VAC
AC Control Voltage 60Hz min.
20.4 VAC
Voltage Utilization Cat. AC-15
230 VAC
Voltage Utilization Cat. DC-13
24 VDC
IP Protection (Terminal Block)
IP20
Max. Switching Capacity
0.08333333333212067
Earth Connection Detection
Yes
AC Control Voltage 50Hz max.
26.4 VAC
AC Control Voltage 60Hz max.
26.4 VAC
Impulse Withstand Voltage (Uimp)
4 kV
Emergency Release Delay
20 ms
Storage/Transport Temperature
-40 ... +85 °C
Integrated System Diagnostics Status
Yes
Pull-In Delay After RESET
20 ms
DC Min. Rated Control Voltage
20.4 VDC
DC Max. Rated Control Voltage
28.8 VDC
Displayed Operating States
Konum relay K2 Konum relay K1 Konum relay K3
Release Delay on Power Failure
80 ms
Number of NC (Normally Closed) Contacts
2
Pull-In Delay on Automatic Start
100 ms