Schmersal SRB202MSL
Order No 101181998
Schmersal Safe Signal Processing Security Relay and Control Modules

SRB202MSL Security Relay and Control Modules

Schmersal SRB202MSL features -25 ... +45 °C ambient temperature, 121 mm depth and 45 mm width.

Product Description

  • • Voltage: 24 VDC
  • • Dimensions: 45mm×100mm×121mm
  • • Weight: 400 g
  • • Contacts: 2 NC

Standards

  • • EN IEC 60947-5-1
  • • EN IEC 61508

Product Features

  • • Muting signalling device monitoring
  • • 2 safety contacts, STOP 0
  • • 2 signal outputs

Technical Specifications

Mounting Fits onto a standard DIN rail per EN 60715
Depth 121 mm
General note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 45 mm
SIL Stop 0 3
Height 100 mm
Number of LEDs 8
Shock resistance 30 g / 11 ms
EMC Class EMC Directive
Application Note Muting function
Mission time 20 Year(s)
Category Stop 0 4
Gross weight 400 g
Housing Material Glass-fibre reinforced thermoplastic, ventilated
Contact material AgSn0, Ag-Ni, self-cleaning, positive drive
Pollution degree 2
Min. cable cross-section 0.25 mm²
Vibration resistance 10...55 Hz, Amplitude 0.35 mm, ± 15 %
DC Level Stop 0 ≥ 99 %
Electronic Fuse Yes
Frequency Range 50 Hz 60 Hz
Clip Tightening Torque 0.6 Nm
Max. cable cross-section 2.5 mm²
PFH Value Stop 0 2.00 x 10⁻⁸ /h
Terminal (Mechanical) Screw terminals
Climatic Resistance EN 60068-2-78
Ripple Voltage 10 %
Stop Category 0
Ambient Temperature -25 ... +45 °C
Operating voltage 24 VDC -10 % / +20 %
Feedback Circuit Yes
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Mechanical life (min.) 10,000,000 Cycles
Note (Contact Resistance) In new condition
Terminal Definitions IEC/EN 60947-1
Reset When Power is Removed Yes
Max. Transmission Resistance 40 Ω
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Connection Diagram Note The relay outputs are suitable for 2-channel control. Automatic start is programmed with X1/X2. The control recognises cross-circuits, wire breakage and earth leakages.
Permitted cable type Single-core rigid / flexible
Number of safety contacts 2
IP Protection (Mounting Area) IP54
Automatic Reset Function Yes
Utilization Category DC-13 2 A
Performance Level Stop 0 e
Number of auxiliary contacts 2
Overvoltage category III
Electrical Power Consumption 5.6 W
Rated operating voltage 24 VDC
Number of Signal Outputs 2
IP Protection (Terminal Block) IP20
Earth Connection Detection Yes
Removable Terminals Yes
Rated impulse withstand voltage (Uimp) 4 kV
Emergency Release Delay 17 ms
Storage/transport temperature -40 ... +85 °C
Integrated System Diagnostics Status Yes
DC Min. Rated Control Voltage 20.4 VDC
Number of Safety Contacts STOP 0 2
Min. Common Cause Failure (CCF) 65
DC Max. Rated Control Voltage 28.8 VDC
Displayed Operating States Position relay K2 Position relay K1 Internal operating voltage Ui Position relay K3 Position relay K5 Muting indicator LA position
Emergency Stop Release Delay (Max.) 20 ms
Release Delay on Power Failure 60 ms
Number of NC (Normally Closed) Contacts 2
Pull-In Delay on Automatic Start 200 ms