Schmersal SRB301HC/R-24V
Order No 101190594
Certificates TÜV cULus CCC TILVA
Schmersal Safe Signal Processing Security Relay and Control Modules

SRB301HC/R-24V Security Relay and Control Modules

Schmersal SRB301HC/R-24V features -25 ... +60 °C ambient temperature and 121 mm depth.

Product Description

  • • Voltage: 24 VDC
  • • Dimensions: 45mm×100mm×121mm
  • • Weight: 290 g
  • • Contacts: 2 NC

Standards

  • • EN IEC 60947-5-1
  • • EN IEC 61508

Product Features

  • • 3 safety contacts, STOP 0
  • • 1 signal output
  • • Suitable for the signal processing of outputs with contact sensors

Technical Specifications

Mounting Fits onto a standard DIN rail per EN 60715
Warning Discontinued product
Depth 121 mm
General note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 45 mm
SIL Stop 0 3
Height 100 mm
Number of LEDs 4
Shock resistance 30 g / 11 ms
EMC Class EMC Directive
Application Note Guard system, emergency stop button, pull-wire emergency stop switches, two-hand control panels, safety mats
Mission time 20 Year(s)
Category Stop 0 4
Gross weight 290 g
Housing Material Glass-fibre reinforced thermoplastic, ventilated
Contact material AgSn0. self-cleaning, positive drive
Start Input Yes
Pollution degree 2
Min. cable cross-section 0.25 mm²
Vibration resistance 10 ... 55 Hz, Amplitude 0.35 mm
DC Level Stop 0 ≥ 99 %
Electronic Fuse Yes
Frequency Range 50 Hz 60 Hz
Clip Tightening Torque 0.6 Nm
Max. cable cross-section 2.5 mm²
PFH Value Stop 0 2.00 x 10⁻⁸ /h
Terminal (Mechanical) Screw terminals
Climatic Resistance EN 60068-2-78
Ripple Voltage 10 %
Stop Category 0
Ambient Temperature -25 ... +60 °C
Reset Edge Detection Yes
Operating voltage 24 VAC -15 % / +10 % 24 VDC -15 % / +40 %
Feedback Circuit Yes
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Mechanical life (min.) 10,000,000 Cycles
Note (Contact Resistance) In new condition
Terminal Definitions IEC/EN 60947-1
Max. Transmission Resistance 40 Ω
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Spare Part Article Number 101193476
Connection Diagram Note Evaluation requirements: switch-off pauses of 250 µs - 1500 µs must be tolerated. The safety sensor's 250 µs switch-off time is extended according to cable length. Typically 500 µs is achieved with 100 m of cable.
Permitted cable type Single-core rigid / flexible
Number of safety contacts 3
IP Protection (Mounting Area) IP54
Current Utilization Cat. AC-15 6 A
Current Utilization Cat. DC-12 0.1 A
Current Utilization Cat. DC-13 6 A
Performance Level Stop 0 e
Number of auxiliary contacts 1
Overvoltage category III
Electrical Power Consumption 3.3 VA
Min. Switching Capacity 10 mA
Rated operating voltage 24 VDC
AC Control Voltage 50Hz min. 20.4 VAC
AC Control Voltage 60Hz min. 20.4 VAC
Voltage Utilization Cat. AC-15 230 VAC
Voltage Utilization Cat. DC-12 24 VDC
Voltage Utilization Cat. DC-13 24 VDC
IP Protection (Terminal Block) IP20
Max. Switching Capacity 2 A
Earth Connection Detection Yes
Removable Terminals Yes
AC Control Voltage 50Hz max. 26.4 VAC
AC Control Voltage 60Hz max. 26.4 VAC
Rated impulse withstand voltage (Uimp) 4 kV
Emergency Release Delay 20 ms
Storage/transport temperature -40 ... +85 °C
Integrated System Diagnostics Status Yes
Pull-In Delay After RESET 20 ms
DC Min. Rated Control Voltage 20.4 VDC
Min. Common Cause Failure (CCF) 65
DC Max. Rated Control Voltage 28.8 VDC
Displayed Operating States Position relay K2 Position relay K1
Release Delay on Power Failure 80 ms
Number of NC (Normally Closed) Contacts 2
Pull-In Delay on Automatic Start 100 ms