Depth
121 mm
Mounting
Snaps onto standard DIN rail to EN 60715
General note
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Width
22.5 mm
EMC rating
EMC-Directive
Height
100 mm
Start input
Yes
Cable Cross-Section
0.25 mm² ... 2.5 mm²
Voltage type
AC | DC
Shock resistance
10 g / 11 ms
Stop-Category
0
Mission time
20 Year(s)
Net Ağırlık
250 g
Number of LEDs
4
Ripple voltage
10 %
Climatic stress
EN 60068-2-78
Electronic Fuse
Yes
Frequency range
50 Hz | 60 Hz
Gross weight
250 g
Category, Stop 0
4
Feedback circuit
Yes
Housing Material
Glass-fibre reinforced thermoplastic, ventilated
Contact material
AgSn0. self-cleaning, positive drive
Pollution degree
2
Min. cable cross-section
0.25 mm²
Operating voltage
24 VAC -15 % / +10 %24 VDC -15 % / +20 %
PFH value, Stop 0
2.00 x 10⁻⁸ /h
Vibration resistance
10...55 Hz, Amplitude 0.35 mm, ± 15 %
Max. cable cross-section
2.5 mm²
Ambient Temperature
-25 ... +45 °C
Mechanical life (min.)
10,000,000
Utilisation category
AC-15 | DC-13
Allowed type of cable
solid single-wire | flexible
Note (Wiring diagram)
The control recognises cross-short, cable break and earth leakages in the monitoring circuit. | Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. | In case of a 1-channel control, connect the NC contact to the operating voltage and bridge S11/S12 and S21/S22. | Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X2. If the feedback circuit is not required, establish a bridge. | Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R); cross-wire monitoring and feedback circuit (H2) | The wiring diagram is shown with guard doors closed and in de-energised condition.
Terminal designations
IEC/EN 60947-1
Terminal connection
Screw terminals
Cross-circuit detection
Yes
Wire breakage detection
Yes
Automatic reset function
Yes
Min. Ortam Sıcaklığı
-25 °C
Note (Delivery capacity)
Not available!
Number of safety contacts
3
Maks. Ortam Sıcaklığı
+45 °C
Note (Contact resistance)
in new state
Earth connection detection
Yes
Indicated operating states
Position relay K1 | Internal operating voltage Ui | Position relay K2
Utilization Category AC-15
6 A | 230 VAC
Utilization Category DC-13
6 A | 24 VDC | 24 VDC / 6 A
Tightening torque of Clips
0.6 Nm
Number of auxiliary contacts
1
Overvoltage category
II | 2
Contact resistance, maximum
0.1 Ω
Nominal Çalışma Voltajı
24 VAC | 24 VDC | 24 VAC -15% / +10% | 24 VDC -15% / +20%, residual ripple max. 10 %
Electrical power consumption
2 W
Note (application conditions)
Safety light curtain | Pull-wire emergency stop switches | Emergency-Stop button | Safety sensor | Guard system
Conduction resistance, maximum
40 Ω
Rated impulse withstand voltage (Uimp)
4 kV
Performance Level, stop 0, up to
e
Depolama / Taşıma Sıcaklığı
-40 ... +85 °C
Pull-in delay at RESET, typically
20 ms
Common Cause Failure (CCF), minimum
65
Integral system diagnostics, status
Yes
Rated control voltage at DC, maximum
28.8 VDC
Number of NC (Normally Closed) Contacts
2
Diagnostic Coverage (DC) Level, Stop 0
≥ 99 %
IP Degree of protection of the enclosure
IP40
Rated control voltage at AC 50 Hz, maximum
26.4 VAC
Rated control voltage at AC 60 Hz, maximum
26.4 VAC
Storage and transport temperature, maximum
+85 °C
Storage and transport temperature, minimum
-40 °C
Rated AC voltage for controls at DC minimum
20.4 VDC
IP Degree of protection of clips or terminals
IP20
Rated AC voltage for controls, 50 Hz, minimum
20.4 VAC
Rated AC voltage for controls, 60 Hz, minimum
20.4 VAC
IP Degree of protection of the installation space
IP54
Drop-out delay in case of power failure, typically
30 ms
Drop-out delay in case of "emergency stop", maximum
30 ms
Pull-in delay at automatic start, maximum, typically
110 ms
Safety Integrity Level (SIL), Stop 0, suitable for applications in
3