SRB301SQ 230V — Schmersal product. Key specifications: Housing Material: Glass-fibre reinforced thermoplastic, ventilated; Ambient Temperature: -25 ... +45 °C; Terminal connection: Screw terminals; Depth: 121 mm; EPLAN: Yes. Article number: 101170100. Request a quote for pricing and lead time; technical data and documents are listed below.

Product Description

  • • Ağırlık: 250 g
  • • Sertifika: cULus TÜV CCC TÜV, cULus,

Standards

  • • EN IEC 60947-5-3
  • • EN IEC 61508
  • • EN IEC 62061
  • • EN ISO 13849-1
  • • EN IEC 60947-5-1
  • • EN IEC 60947-5-5
  • • EN IEC 60204-1
  • • EN IEC 60947-1

Product Features

  • • 3 safety contacts, STOP 0
  • • 1 Signalling output
  • • Suitable for the signal processing of outputs with contact sensors

Technical Specifications

Depth 121 mm
EPLAN Yes
Mounting Snaps onto standard DIN rail to EN 60715
Category 4
General note Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Width 22.5 mm
PFH value 2.00 x 10⁻⁸ /h
EMC rating EMC-Directive
Height 100 mm
Start input Yes
Cable Cross-Section 0.25 mm² ... 2.5 mm²
Shock resistance 30 g / 11 ms
Stop-Category 0
Mission time 20 Year(s)
Net Ağırlık 250 g
Number of LEDs 3
Climatic stress EN 60068-2-78
Electronic Fuse Yes
Frequency range 50 Hz | 60 Hz
Gross weight 250 g
Feedback circuit Yes
Housing Material Glass-fibre reinforced thermoplastic, ventilated
Contact material AgSn0. self-cleaning, positive drive
Pollution degree 2
Min. cable cross-section 0.25 mm²
Operating voltage 48 ... 240 VAC
Vibration resistance 10 ... 55 Hz, Amplitude 0.35 mm
Max. cable cross-section 2.5 mm²
Ambient Temperature -25 ... +45 °C
Performance level e
Removable Terminals Yes
Mechanical life (min.) 10,000,000
Reset edge detection Yes
Utilisation category AC-15 | DC-13
Allowed type of cable solid single-wire | flexible
Note (Wiring diagram) Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals S12/X3. If the feedback circuit is not required, establish a bridge. | The control recognises cross-short, cable break and earth leakages in the monitoring circuit. | Relay outputs: Suitable for 2 channel control, for increase in capacity or number of contacts by means of contactors or relays with positive-guided contacts. | Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R); cross-wire monitoring and feedback circuit (H2) | The wiring diagram is shown with guard doors closed and in de-energised condition.
Terminal designations IEC/EN 60947-1
Type of voltage range AC
Terminal connection Screw terminals
Cross-circuit detection Yes
Wire breakage detection Yes
Automatic reset function Yes
Min. Ortam Sıcaklığı -25 °C
Note (Delivery capacity) Not available!
Number of safety contacts 3
Maks. Ortam Sıcaklığı +45 °C
Note (Contact resistance) in new state
Earth connection detection Yes
Indicated operating states Position relay K1 | Position relay K2
Utilization Category AC-15 6 A | 230 VAC
Utilization Category DC-13 6 A | 24 VDC | 24 VDC / 6 A
Tightening torque of Clips 0.6 Nm
Number of auxiliary contacts 1
Overvoltage category II | 2
Contact resistance, maximum 0.1 Ω
Nominal Çalışma Voltajı 48 ... 240 VAC
Electrical power consumption 2.8 VA
Switching frequency, maximum 5 Hz
Note (application conditions) Pull-wire emergency stop switches | Emergency-Stop button | Guard system
Conduction resistance, maximum 40 Ω
Rated impulse withstand voltage (Uimp) 4 kV
Diagnostic Coverage (DC) Level > 99 %
Depolama / Taşıma Sıcaklığı -40 ... +85 °C
Pull-in delay at RESET, typically 15 ms
Common Cause Failure (CCF), minimum 65
Integral system diagnostics, status Yes
Number of NC (Normally Closed) Contacts 2
IP Degree of protection of the enclosure IP40
Pull-in delay at automatic start, maximum 35 ms
Rated control voltage at AC 50 Hz, maximum 240 VAC
Rated control voltage at AC 60 Hz, maximum 240 VAC
Storage and transport temperature, maximum +85 °C
Storage and transport temperature, minimum -40 °C
IP Degree of protection of clips or terminals IP20
Rated AC voltage for controls, 50 Hz, minimum 48 VAC
Rated AC voltage for controls, 60 Hz, minimum 48 VAC
Drop-out delay in case of emergency, typically 20 ms
IP Degree of protection of the installation space IP54
Drop-out delay in case of "emergency stop", maximum 25 ms
Pull-in delay at automatic start, maximum, typically 30 ms
Safety Integrity Level (SIL), suitable for applications in 3