Schmersal SRB301ST/CC-24V-(V.2)
Order No 103002037
Certificates TÜV cULus TILVA
Schmersal Safe Signal Processing Security Relay and Control Modules

SRB301ST/CC-24V-(V.2) Security Relay and Control Modules

Schmersal SRB301ST/CC-24V-(V.2) features -25 ... +60 °C ambient temperature and 121 mm depth.

Product Description

  • • Voltage: 24 VDC
  • • Dimensions: 22.5mm×120mm×121mm
  • • Weight: 250 g
  • • Contacts: 2 NC

Standards

  • • EN ISO 13849-1
  • • EN IEC 62061
  • • EN IEC 61508

Product Features

  • • Plug-in spring-cage
  • • Suitable for the signal processing of outputs with contact sensors
  • • Suitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains
  • • 3 safety contacts, STOP 0
  • • 1 signal output

Technical Specifications

Mounting Fits onto a standard DIN rail per EN 60715
Warning Discontinued product
Depth 121 mm
General note Inductive loads (e.g. contactors, relays, etc.) must be suppressed with a suitable circuit.
Width 22.5 mm
SIL Stop 0 3
Height 120 mm
Number of LEDs 5
Shock resistance 10 g / 11 ms
EMC Class EMC Directive
Application Note Safety sensor, guard system, emergency stop button, pull-wire emergency stop switches, safety light barriers
Mission time 20 Year(s)
Category Stop 0 4
Gross weight 250 g
Housing Material Glass-fibre reinforced thermoplastic, ventilated
Contact material AgSn0. self-cleaning, positive drive
Start Input Yes
Pollution degree 2
Min. cable cross-section 0.25 mm²
Vibration resistance 10 ... 55 Hz, Amplitude 0.35 mm
DC Level Stop 0 ≥ 99 %
Electronic Fuse Yes
Frequency Range 50 Hz 60 Hz
Max. cable cross-section 1.5 mm²
PFH Value Stop 0 2.00 x 10⁻⁸ /h
Terminal (Mechanical) Removable cage terminals
Climatic Resistance EN 60068-2-78
Ripple Voltage 10 %
Stop Category 0
Ambient Temperature -25 ... +60 °C
Reset Edge Detection Yes
Operating voltage 24 VAC -15 % / +10 % 24 VDC -15 % / +40 %
Feedback Circuit Yes
IP Protection (Housing) IP40
Max. Contact Resistance 0.1 Ω
Mechanical life (min.) 10,000,000 Cycles
Note (Contact Resistance) In new condition
Terminal Definitions IEC/EN 60947-1
Max. Transmission Resistance 40 Ω
Wire Breakage Detection Yes
Cross-Circuit Detection Yes
Connection Diagram Note The wiring diagram is shown with guard doors closed and in the de-energised condition. nQS (top): no cross-wire protection. QS (bottom): cross-wire protection. Automatic start is programmed by connecting terminals S12/X3. F1 = Hybrid fuse
Max. installation altitude 2,000 m
Permitted cable type Single-core rigid / flexible
Number of safety contacts 3
IP Protection (Mounting Area) IP54
Automatic Reset Function Yes
Current Utilization Cat. AC-15 6 A
Current Utilization Cat. DC-13 6 A
Performance Level Stop 0 e
Number of auxiliary contacts 1
Overvoltage category III
Electrical Power Consumption 4.9 VA
Min. Switching Capacity 10 mA
Rated operating voltage 24 VDC
AC Control Voltage 50Hz min. 20.4 VAC
AC Control Voltage 60Hz min. 20.4 VAC
Voltage Utilization Cat. AC-15 230 VAC
Voltage Utilization Cat. DC-13 24 VDC
IP Protection (Terminal Block) IP20
Max. Switching Capacity 2 A
Earth Connection Detection Yes
Removable Terminals Yes
AC Control Voltage 50Hz max. 26.4 VAC
AC Control Voltage 60Hz max. 26.4 VAC
Rated impulse withstand voltage (Uimp) 4 kV
Emergency Release Delay 25 ms
Storage/transport temperature -40 ... +85 °C
Integrated System Diagnostics Status Yes
Pull-In Delay After RESET 15 ms
DC Min. Rated Control Voltage 20.4 VDC
Min. Common Cause Failure (CCF) 65
DC Max. Rated Control Voltage 28.8 VDC
Displayed Operating States Position relay K2 Position relay K1 Internal operating voltage Ui Operating voltage UB
Emergency Stop Release Delay (Max.) 32 ms
Release Delay on Power Failure 100 ms
Number of NC (Normally Closed) Contacts 2
Pull-In Delay on Automatic Start 100 ms
Note (LED Switching Condition Indication) QS: cross-wire short detection status (LED on when cross-wire short detection active).